Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop B
Sequence Number 3
Notes
Date Text
2003-05-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031228
 ADD: 4011 NORTH SHORE DRIVE
 CONT: DON CLAY
 TEL: (561)683-0609
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) COUNTY AMENDMENT 105.3 (5) SPECIAL
 INSPECTOR PROGRAM: TO REGISTER WITH DON
 NEELY, THRESHOLD & RESIDENT INSPECTOR
 COORDINATOR 805-6665.
 FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
 105'X72'=7560 SQ FT, 7650@ 15=504 OCC.
 NET AND STAGE NOT INCLUDED.
  
 NOTE: IMPACT FEES PAID UNDER PERMIT
 # 9908 0492 APRIL 4, 2000. REV# 00-12234
  
 2) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY. PROVIDE INFORMATION
 PER ROOM OR EGRESS REQUIREMENTS.
  
 3) PLANS INDICATE THE USE OF FIRE SPRINK
 LERS, AS WELL AS THE BUILDING AREA FOR
 EDUCATIONAL USAGE (TABLE 600) NO FIRE
 SPRINKLER PLANS ARE INCLUDED IN THIS
 PACKAGE.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-1, THE PLANS INDICATE A LOT OF
 3'-0" DOORS DRAWN IN AT 2'-0". FLORIDA
 ACCESSIBILITY, REQUIRED MANEUVERING
 CLEARENCES AT DOORS ARE NOT MET, THERE
 IS NO 5'-0" TURNING RADIUS IN THE BATH-
 ROOMS, OR EVEN ENOUGH ROOM TO GET A
 WHEELCHAIR PAST THE ONE ENTRY DOOR
 CLOSEST TO THE WATER CLOSET. PLANS INDIC
 ATE A "JUNIOR SIZE " WATER CLOSET IS TO
 BE USED, PROVIDE ADDITIONAL INFORMATION.
 PROVIDE PATH OF ACCESSIBILITY.
 THE 2'-0" WIDE DOOR IS ALSO AND ISSUE
 AT THE WATER CLOSET AT THE SHOWERS.
  
 P-1 DRAWINGS INDICATE STALL DOORS TO BE
 24" WIDE VS 32" REQUIRED.
  
 5) PROVIDE INFORMATION FOR AN ACCESSIBLE
 DINING ROOM? 11.5.4 ARE THE TABLES BENCH
 TYPE WITH FIXED SEATING, OR ARE CHAIRS
 REMOVABLE?
  
 6)11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL. PROVIDE MANUFACTURERS SPEC
 ON CHAIRLIFT. IS THIS MODEL PERMANENT OR
 PORTABLE? IF PORTABLE WHERE WILL IT BE
 STORED WHEN NOT REQUIRED?
  
 7) REQUIRED CORRECTIONS? TITLE SHEET,
 2002 FLORIDA BUILDING CODE.
  
 8) 2111.1.9 1 1/2" RECESS A WATERSTOP IS
 REQUIRED FOR EXTERIOR WALLS. PLANS ARE
 TO INDICATE THIS. IF SLAB IS POURED AND
 A WATERSTOP IS NOT PRESENT HOW WILL THIS
 BE CORRECTED?
  
 9) MISSING WINDOW SCHEDULE, SHEET A-24
 INDICATES THE USE OF EITHER CASEMENT OR
 HORIZONTAL ROLLING WINDOWS? PRODUCT TEST
 ING REPORTS SUBMITTED ARE FOR SINGLE
 HUNG WINDOWS. THERE IS NO WAY TO INTER-
 PET IF MULLIONS ARE TO BE REQUIRED?
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) WINDOW MULLIONS
 B) ROOFING ASSEMBLIES, FLAT AND SLOPED
 ROOFING MATERIALS
  
 11) COMPONENTS & CLADDING SHEET A-23
 THE PRESSURES GIVEN UNDER THIS CHART ARE
 AT AN IMPORTANCE FACTOR OF (1). THIS
 BUILDING IS TO BE DESIGNED AT A IMPORT-
 ANCE FACTOR OF 1.15!!! PRESSURES INDI-
 CATED ARE LOW!!!!
  
 GYMNASIUM:
 12) 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 DOUBLE GYMNASIUM DOORS SWING IN THE
 WRONG DIRECTION, OR EACH LEAF SWING IN
 THE DIRECTION OF TRAVEL.
  
 13) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-5 DETAIL (3) DOESN'T INDICATE
 THE SIZE OF THE ANCHOR BOLTS DIA OR
 LENGHT?
  
 14) NEW 2001 FBC 2117.1.2 CATHEDRAL END-
 WALLS, GABLE ENDWALLS ADJACENT TO CATHED
 RAL CEILINGS SHALL BE CONTINIOUS FROM
 THE UPPERMOST FLOOR TO THE CEILING
 DIAPHRAM OR TO THE ROOF DIAPHRAM.
  
 15) TRUSS I JOIST:ITEM (27) FIRST REVIEW
 (A-F) HAVE NOT BEEN ADDRESSED!
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026