| 2003-05-29 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03031228 |
| | ADD: 4011 NORTH SHORE DRIVE |
| | CONT: DON CLAY |
| | TEL: (561)683-0609 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) COUNTY AMENDMENT 105.3 (5) SPECIAL |
| | INSPECTOR PROGRAM: TO REGISTER WITH DON |
| | NEELY, THRESHOLD & RESIDENT INSPECTOR |
| | COORDINATOR 805-6665. |
| | FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | 105'X72'=7560 SQ FT, 7650@ 15=504 OCC. |
| | NET AND STAGE NOT INCLUDED. |
| | |
| | NOTE: IMPACT FEES PAID UNDER PERMIT |
| | # 9908 0492 APRIL 4, 2000. REV# 00-12234 |
| | |
| | 2) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY. PROVIDE INFORMATION |
| | PER ROOM OR EGRESS REQUIREMENTS. |
| | |
| | 3) PLANS INDICATE THE USE OF FIRE SPRINK |
| | LERS, AS WELL AS THE BUILDING AREA FOR |
| | EDUCATIONAL USAGE (TABLE 600) NO FIRE |
| | SPRINKLER PLANS ARE INCLUDED IN THIS |
| | PACKAGE. |
| | |
| | 4)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A-1, THE PLANS INDICATE A LOT OF |
| | 3'-0" DOORS DRAWN IN AT 2'-0". FLORIDA |
| | ACCESSIBILITY, REQUIRED MANEUVERING |
| | CLEARENCES AT DOORS ARE NOT MET, THERE |
| | IS NO 5'-0" TURNING RADIUS IN THE BATH- |
| | ROOMS, OR EVEN ENOUGH ROOM TO GET A |
| | WHEELCHAIR PAST THE ONE ENTRY DOOR |
| | CLOSEST TO THE WATER CLOSET. PLANS INDIC |
| | ATE A "JUNIOR SIZE " WATER CLOSET IS TO |
| | BE USED, PROVIDE ADDITIONAL INFORMATION. |
| | PROVIDE PATH OF ACCESSIBILITY. |
| | THE 2'-0" WIDE DOOR IS ALSO AND ISSUE |
| | AT THE WATER CLOSET AT THE SHOWERS. |
| | |
| | P-1 DRAWINGS INDICATE STALL DOORS TO BE |
| | 24" WIDE VS 32" REQUIRED. |
| | |
| | 5) PROVIDE INFORMATION FOR AN ACCESSIBLE |
| | DINING ROOM? 11.5.4 ARE THE TABLES BENCH |
| | TYPE WITH FIXED SEATING, OR ARE CHAIRS |
| | REMOVABLE? |
| | |
| | 6)11-4.1.2 VERTICAL ACCESSIBILITY, |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | STRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. PROVIDE MANUFACTURERS SPEC |
| | ON CHAIRLIFT. IS THIS MODEL PERMANENT OR |
| | PORTABLE? IF PORTABLE WHERE WILL IT BE |
| | STORED WHEN NOT REQUIRED? |
| | |
| | 7) REQUIRED CORRECTIONS? TITLE SHEET, |
| | 2002 FLORIDA BUILDING CODE. |
| | |
| | 8) 2111.1.9 1 1/2" RECESS A WATERSTOP IS |
| | REQUIRED FOR EXTERIOR WALLS. PLANS ARE |
| | TO INDICATE THIS. IF SLAB IS POURED AND |
| | A WATERSTOP IS NOT PRESENT HOW WILL THIS |
| | BE CORRECTED? |
| | |
| | 9) MISSING WINDOW SCHEDULE, SHEET A-24 |
| | INDICATES THE USE OF EITHER CASEMENT OR |
| | HORIZONTAL ROLLING WINDOWS? PRODUCT TEST |
| | ING REPORTS SUBMITTED ARE FOR SINGLE |
| | HUNG WINDOWS. THERE IS NO WAY TO INTER- |
| | PET IF MULLIONS ARE TO BE REQUIRED? |
| | |
| | 10)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING REPORTS: |
| | A) WINDOW MULLIONS |
| | B) ROOFING ASSEMBLIES, FLAT AND SLOPED |
| | ROOFING MATERIALS |
| | |
| | 11) COMPONENTS & CLADDING SHEET A-23 |
| | THE PRESSURES GIVEN UNDER THIS CHART ARE |
| | AT AN IMPORTANCE FACTOR OF (1). THIS |
| | BUILDING IS TO BE DESIGNED AT A IMPORT- |
| | ANCE FACTOR OF 1.15!!! PRESSURES INDI- |
| | CATED ARE LOW!!!! |
| | |
| | GYMNASIUM: |
| | 12) 1012.1.2 EGRESS DOORS SHALL BE SIDE |
| | SWINGING TYPE. DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS FOR THE FOLLOWING: |
| | DOUBLE GYMNASIUM DOORS SWING IN THE |
| | WRONG DIRECTION, OR EACH LEAF SWING IN |
| | THE DIRECTION OF TRAVEL. |
| | |
| | 13) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A-5 DETAIL (3) DOESN'T INDICATE |
| | THE SIZE OF THE ANCHOR BOLTS DIA OR |
| | LENGHT? |
| | |
| | 14) NEW 2001 FBC 2117.1.2 CATHEDRAL END- |
| | WALLS, GABLE ENDWALLS ADJACENT TO CATHED |
| | RAL CEILINGS SHALL BE CONTINIOUS FROM |
| | THE UPPERMOST FLOOR TO THE CEILING |
| | DIAPHRAM OR TO THE ROOF DIAPHRAM. |
| | |
| | 15) TRUSS I JOIST:ITEM (27) FIRST REVIEW |
| | (A-F) HAVE NOT BEEN ADDRESSED! |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |