Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop P
Sequence Number 2
Notes
Date Text
2003-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 ADMIN. CODE, CHAPTER
 ONE & AMENDMENTS.
  
 1) PLANS SHALL BE ROUTED TO THE PALM
 BEACH HEALTH UNIT DIVISION OF ENVIRON-
 MENTAL HEALTH, 901 EVERNIA ST. WPB
 (561) 355-3018. PLANS SHALL BE STAMPED
 PRIOR TO RESUBMITTING. FBC-2001 101.4.7
 2) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURES PER TABLE 1003.1 (BLDG CODE), AND
 TABLE 403.1 (PLMG. CODE). SHOW SQUARE
 FOOTAGE FOR EACH OCCUPANCY AND REQUIRED
 FIXTURES FOR EACH.
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF
 ALL VERTICAL WALLS, INCLUDING PARAPETS.
 SHOW ALL AREAS OF ROOFS THAT DRAIN ON TO
 THE ROOF FROM ABOVE. (GYM ROOF) SECTIONS
 1106, 1107, AND ALL SUBSECTIONS.
 *COVER SHEET INDICATES 31 3" ROOF DRAINS
 BUT THERE ARE ONLY 26 3" ROOF DRAINS AND
 6 2" ROOF DRAINS. PLEASE CLAIRFY. - IN-
 DICATE SQUARE FOOTAGE BEING DRAINED BY
 EACH ROOF DRAIN.
 4) PLEASE SUBMIT A DETAIL FOR THE SCUPP-
 ERS. SHOW HEIGHT AND WIDTH FOR OPENING
 AND INDICATE HEIGHT OFF ROOF TO FLOW
 LINE PER SECTION 1511.6.4.3 OF THE BLDG
 CODE.
 5) PLEASE SUBMIT A STORM RISER DIAGRAM,
 SHOWING ALL PIPE SIZES AND INDICATE
 WHERE THEY TERMINATE.
 6) ALL PUBLIC AND COMMON AREA TOILET
 ROOMS SHALL COMPLY WITH 11-4.22 AND ALL
 SUBSECTIONS. PLEASE PROVIDE A DETAIL FOR
 EACH TOILET ROOM. SHOW TURNING CIRCLE &
 CLEAR FLOOR SPACE. (SEE FIGS. 3,28,29 &
 32). SECTION 11-4.1.3(11)
 7) PLEASE SUBMIT A DETAIL FOR TOILET
 ROOM BETWEEN CLASSROOMS #1 & #2 AND FOR
 TOILET ROOM BETWEEN CLASSROOMS #12 & #13
 SHOW ALL DIMENTIONS FOR TOILET ROOMS.
 TOILET ROOMS SHALL COMPLY WITH 11-4.22
 8) YOU MUST COMPLETE A WAIVER FOR THE
 USE OF CHILDREN'S FIXTURES IN THE SCHOOL
 THE ACCESSIBILITY STANDARD IS ONLY A
 GUIDLINE AND HAS NOT BEEN ADOPTED BY THE
 DEPT. OF JUSTICE. THE WAIVER SHALL BE
 SUBMITTED TO STATE OF FLA. DEPT. OF COMM
 AFFAIRS. (PLEASE SUBMIT CUT SHEETS FOR
 CHILDRENS FIXTURES,
 9) SHT P-1 PLEASE PROVIDE DETAIL FOR
 TEACHERS LOUNGE SINK. SHOW COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 10) SHT P-5 SHUT OFF VALVES REQUIRED FOR
 ALL WALL HYDRANTS. SECTION 606.2(2)
 PLEASE SHOW ON WATER RISER DIAGRAM.
 11) SHT P-5 WATER HEATERS, PRV DISCHARGE
 LINE SHALL NOT HAVE ANY TRAPPED SECTIONS
 SECTION 504.7.1 - WATER RISER STILL IN-
 DICATES THAT THE LINES WILL BE TRAPPED.
 PLEASE SHOW DETAIL FOR T/P LINES SHOWING
 HOW THEY WILL BE PIPED TO COMPLY WITH
 CODE REFERENCE. ALSO INDICATE THAT
 THERMAL EXPANSION CONTROL PER 607.3.2
 IS BEING ADDRESSED. SUBMIT DETAIL.
 12) RPZ BACKFLOW REQUIRED ON WATER SERV.
 PLEASE INDICATE ON WATER RISER DIAGRAM
 SHT P-5. SECTION 608.13.2 & UTILITY ORD.
 13) TOILET ROOM IN PRESIDENTS SHALL BE
 EITHER ACCESSIBLE (11-4.22) OR ADAPTABLE
 PLEASE INDICATE ON PLANS. IF ADAPTABLE,
 DETAIL REQUIRED SHOWING 5' TURNING
 CIRCLE AND BACKING AS REQUIRED IN SEC.
 11-4.22
 14) SHT A-1 PLEASE INDICATE HOW THE
 TOILET IN THE ISOLATION ROOM WILL BE
 ACCESSIBLE.
 15) PLEASE SHOW ALL CLEANOUTS REQUIRED
 BY SECTIONS 708.3.1, 708.3.3, & 708.3.5
 ON THE SANITARY RISER DIAGRAM.
 ********WHEN RESUBMITTING PLANS*********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved