2003-04-11 00:00:00 
 CONTINUATION OF BUILDING PLAN REVIEW
 DATED 3/11/2003
 COMMENTS:
 18) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 19) SHEET A-10, A-11 & A-12EXTERIOR
 WALLS ARE MISSING THE 1 1/2" RECESS
 FOR BLOCK WORK AT FLOOR LEVEL.
  
 20) MISSING A WINDOW SCHEDULE, SHEET
 A-24, WHAT TYPE OF WINDOWS WILL BE USED
 WHERE.
  
 21)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOW MULLIONS
 B) ROOFING ASSEMBLIES, FLAT ROOF &
 SLOPED ROOFS
  
 22) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 23) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
  
 24) GYMNASIUM 105'X72'=7560 SQ FT
 OCCUPANT LOAD: 7560 @ 15= 504 ALLOWABLE
 TABLE 1606 :
 BUILDINGS AND STRUCTURES WHERE THE OCCU-
 PANT LOAD IS 300 OR MORE IN ONE ROOM.
 IMPORTANCE FACTOR 1.15 CORRECT: COVER-
 SHEET.
  
 25) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-5 DETAILS DO NOT INDICATE
 WHAT SIZE DIA OR LENGHT ANCHOR BOLTS
 THAT ARE TOBE EMBEDDED INTO THE CONCRETE
 NOR IS THERE INFORMATION ON THE BOLTS
 THAT ARE TO GO THROUGH THE BOTTOM PLATE
 THROUGH THE WOOD ARCH. SHEET A-16 GIVES
 A DETAIL FOR THE BOTTOM PLATE BUT NOT EN
 OUGH INFORMATION, WHAT SIZE WELDS ARE
 TO BE USED?
  
 26) NEW 2001 FBC! 2117.1.2 CATHEDRAL
 ENDWALLS, GABLE ENDWALLS ADJACENT TO
 CATHEDRAL CEILINGS SHALL BE CONTINUOUS
 FROM THE UPPERMOST FLOOR TO THE CEILING
 DIAPHRAM OR TO THE ROOF DIAPGRAM.
  
 27) TRUSS I JOIST:
 A) MISSING THE MANUFACTURERS SPECS &
 ROOF SPAN CHARTS?
 B) PROVIDE CURRENT 2003 MANUFACTURERS
 INFORMATION FOR FRAMING CONNECTION, TOP
 MOUNT VERSES FACE MOUNT.
 C) PROVIDE INFORMATION FROM THE TRUSS
 JOIST MANUFACTURER THAT THE I-JOIST DO
 NOT NEED TO SIT PERPENDICULAR BUT
 PERPENDICULAR TO THE SLOPE OF THE ROOF.
 I-JOIST ACTING AS PURLINS. HOW WILL THE
 ACCENTRIC LOADING OF THE BOTTOM CORD
 BE HANDLED SINCE DETAIL 10/A-15 THE
 OUTLOOKERS DO NOT ATTACH TO THE BOTTOM
 CORD OF THE I-JOIST? ALSO HOW ARE THE
 F-2 VALUES TRANSFERED INTO THE OUTTOOK-
 ERS, A H-10 CONNECTOR SPECIFIED IN
 DETAIL 01/A-18?WHAT MANUFACTURER?
 D) ARE WEB STIFFENERS REQUIRED? AT WHAT
 SPACING WILL THE SOLID BRIDGING BE
 INSTALLED?
 E) PLANS INDICATE A VENTED SOFFIT AS RE-
 QUIRED 2309.7.1.HOW WILL THE INTERIOR
 JOIST BE VENTED SINCE THIS DESIGN IS
 SOLID WOOD JOIST NOT OPEN WEB TRUSSES?
 F) OUTLOOKERS WHAT TYPE OF CONNECTION
 WILL BE MADE TO THE I-JOIST?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026