2003-04-10 00:00:00PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.PLEASE INDICATE WHAT WILL BE STORED
 IN THE STORAGE ROOMS SHOWN ON PLAN SHEET
 A-1.
  
 2.PLAN SHEET A-1 INDICATES TWO STORAGE
 ROOMS.THE MECHANICAL PLAN DOES NOT
 INDICATE ANY TYPE OF VENTILATION.WILL
 THIS BE ACCOMPLISHED BY NATURAL MEANS
 OR MECHANICALLY?PLAN DOES NOT SHOW ANY
 LOUVERED DOORS OR LOUVERS.SEE 2001
 FBC(M) 404.
  
 3.PLAN SHEET M-2 NOTE H, AHU CEILING
 MOUNT IN FIRE RATED ENCLOUSURE.FIRE
 DAMPER NOT INDICATED ON PLAN SHEET M-1
 OR IN THE NOTES.PLEASE NOTE, ENCLOSURE
 SHALL BE LARGE ENOUGH TO ACCESS FOR
 SERVICE AND MAINTENANCE.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION & WALK-IN COOLERS.
 PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  