| 2003-04-10 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.PLEASE INDICATE WHAT WILL BE STORED | | | IN THE STORAGE ROOMS SHOWN ON PLAN SHEET | | | A-1. | | | | | | 2.PLAN SHEET A-1 INDICATES TWO STORAGE | | | ROOMS.THE MECHANICAL PLAN DOES NOT | | | INDICATE ANY TYPE OF VENTILATION.WILL | | | THIS BE ACCOMPLISHED BY NATURAL MEANS | | | OR MECHANICALLY?PLAN DOES NOT SHOW ANY | | | LOUVERED DOORS OR LOUVERS.SEE 2001 | | | FBC(M) 404. | | | | | | 3.PLAN SHEET M-2 NOTE H, AHU CEILING | | | MOUNT IN FIRE RATED ENCLOUSURE.FIRE | | | DAMPER NOT INDICATED ON PLAN SHEET M-1 | | | OR IN THE NOTES.PLEASE NOTE, ENCLOSURE | | | SHALL BE LARGE ENOUGH TO ACCESS FOR | | | SERVICE AND MAINTENANCE. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPPRESSION & WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719 |
|