| Plan Review Notes For Permit 03031228 |
| Permit Number |
03031228 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-27 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MDP AND | | | SUB-PANELS. SIZE PER 250-122 | | | | | | 2)NOTE: PLEASE CORRELATEMDP AND RISER. | | | RISER MENTIONS A 800A MAINS AND MDP | | | SHOWS MLO? | | | | | | | | | PLEASE CORRECT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | [email protected] | | | 561-659-8096 EXT 8372 |
|