Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-27 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MDP AND
 SUB-PANELS. SIZE PER 250-122
  
 2)NOTE: PLEASE CORRELATEMDP AND RISER.
 RISER MENTIONS A 800A MAINS AND MDP
 SHOWS MLO?
  
  
 PLEASE CORRECT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  