Plan Review Notes
Plan Review Notes For Permit 03031228
Permit Number 03031228
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-11 00:00:00 
  
  
 BUILDING PLAN REVIEW
 PERMIT: 03031228
 ADD: 4011 NORTH SHORE DR
 CONT: DON CLAY CONSTRUCTION
 TEL: (561)683-0609
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) COUNTY AMENDMENTS: 105.3(5)
 SPECIAL INSPECTOR PROGRAM, BUILDINGS >
 20,000 SQ. FT.
 SPECIAL INSPECTOR TO REGISTER WITH
 DON NEELY THE SPECIAL INSPECTOR &
 THRESHOLD INSPECTOR COORDINATOR AT
 659-6700 X6665
  
 NOTE PROVIDE (3) COPIES OF DOCUMENTS FOR
 THE PERMITED SET OF PLANS.
  
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLANS ARE NOT CLEAR AS TO THE FOUNDA
 TION, AREAL PHOTOS INDICATE AN EXISTING
 SLAB. IS THIS SLAB TO BE REMOVED? IF NOT
 THIS SLAB HAS TO BE CERTIFIED BY THE
 ENGINEER THAT IT WILL ACCEPT THE LOADS
 BEING IMPOSED ON IT!
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SOILS REPORT SIGNED/ SEALED BY SOILS
 ENGINEER.
  
 4) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 IF COUNTY IMPACT FEES WERE PAID UNDER
 THE OLD CANCEALED PERMIT, THE PLANS
 STILL NEED TO SUBMITTED TO THE COUNTY
 FOR REVIEW AND STAMPING!
  
 6)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 7) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 8)1005.4 EMERGENCY ESCAPE AND RESCUE
 OPENINGS,
 (2) EVERY ROOM OR SPACE GREATER THAN
 250 FT USED FOR CLASSROOM OR OTHER ED-
 UCATIONAL PURPOSES OR NORMALLY SUBJECT
 TO STUDENT OCCUPANCY, AND EVERY ROOM
 SUBJECT TO CLIENT OCCUPNCY SHALL NOT
 HAVE NOT LESS THAN ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE, SEE EXCEPTIONSALSO
 EXCEPTION #1 AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, PLANS INDICATE THERE
 SHALL BE ONE, BUT NO PLANS WERE SUBMIT-
 TED?
  
 9)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-1 THE PLANS INDICATE ALOT OF THE
 3'-0" DOORS BEING DRAWN IN AS A 2'-0"
 DOOR, THIS MAY CAUSE PROBLEMS WITH THE
 REQUIRED MANEUVERING CLEARENECES AT
 DOORS, (11-4.13.6) DOORS 27 & 42 DO NOT
 HAVE THE REQUIRED 18" ON THE LATCH SIDE!
 THE DOORWAYS DRAWN IN AS 2'-0" MAY ALSO
 RUN INTO THESE SAME PROBLEMS, PLEASE
 REVIEW?
  
 10) ACCESSIBLE MEANS OF EGRESS,
 11-4.1.3(8), (9)
 ALL CLASSROOMS HAVING EXTERIOR DOORS &
 LANDINGS SHOULD BE MADE TO BE ACCESSIBLE
 LANDINGS NO LOWER THAN 1/2" BELOW THE
 INTERIOR FINISH FLOOR. SHEET A-3 DETAIL
 11/A5 A CUT SECTION THRU A EXTERIOR DOOR
 AND STOOP. STOOP ELEVATION MISSING FROM
 THE CUT SECTION? SHEET A-10 NOTES: INDIC
 ATE SLOPED SIDEWALKS TO MEET ADA GUIDE-
 LINES, THIS SHOULD ALSO INCLUDE THE
 EXTERIOR DOOR LANDINGS. LANDINGS NEED TO
 BE BIG ENOUGH FOR TURNING RADIUS, AND
 THE DRADE NEEDS TO BE TO THE TOP OF THE
 LANDING FOR ACCESSIBILITY, WITH POSITIVE
 SLOPE AWAY FROM THE BUILDING.
  
 11) BUILDING SIGNAGE: 11-4.1.3(16)(A)(B)
 SIGNS WHICH DESIGNATE PERMANENT ROOMS &
 SPACESSHALL COMPLY WITH 11-4.30.1,
 11-4.30.4, 11-4.30.(5-6).
 B) OTHER SIGNS WHICH PROVIDE DIRECTION
 TO OR INFORMATION ABOUT FUNCTION SPACES
 OF THE BUILDING SHALL COMPLY WITH:
 11-4.30.1, 11-4.30.2, 11-4-30.3 & 11-4.5
  
 12) PROVIDE INFORMATION FOR AN ACCESS-
 IBLE DINING ROOM 11.5.4.
  
 13) 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
 PROVIDE INFORMATION FOR VERTICAL
 LIFT ONTO THE STAGE.
  
 14)11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOLIET ROOMS SHALL COMPLY
 WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 ROOM # 35 GIRLS HANDICAPPED STALL OVER
 LAPPING DOOR SWING INTO CLEARTHE CLEAR
 FLOOR SPACE.
  
 15) 1021.4(NEW UNDER 2001 FBC) DOORS
 THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE RECESSED TO PREVENT INTERFE-
 ENCE WITH CORRIDOR TRAFFIC: ANY DOORS
 NOT RECESSED SHALL OPEN 180 DEGREES TO
 STOP AGAINST THE WALL. DOORS IN ANY POSI
 TION SHALL NOT REDUCE THE REGUIRED CORRI
 DOR WIDTH BY MORE THAN ONE HALF.
  
 16) REQUIRED CORRECTIONS:
 A) TITLE SHEET 2002 FLORIDA BUILDING
 CODE
 B) SHEET A-5, REFRENCE TO STANDARD
 BUILDING CODE
 C) SHEET A-5 BASIC WIND VELOCITY 110
  
 17)COVER SHEET MISSING :
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING # (4) INTERNAL PRESSURE COEF.
  
 NOTE: PLAN REWIEW ALLOWS FOR 200
 LINES, ANOTHER"BUILDING PLAN REVIEW"
 WILL NEED TO BE OPENED TO CONTINUE
 COMMENTS.