| | BUILDING PLAN REVIEW |
| | PERMIT: 03031228 |
| | ADD: 4011 NORTH SHORE DR |
| | CONT: DON CLAY CONSTRUCTION |
| | TEL: (561)683-0609 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) COUNTY AMENDMENTS: 105.3(5) |
| | SPECIAL INSPECTOR PROGRAM, BUILDINGS > |
| | 20,000 SQ. FT. |
| | SPECIAL INSPECTOR TO REGISTER WITH |
| | DON NEELY THE SPECIAL INSPECTOR & |
| | THRESHOLD INSPECTOR COORDINATOR AT |
| | 659-6700 X6665 |
| | |
| | NOTE PROVIDE (3) COPIES OF DOCUMENTS FOR |
| | THE PERMITED SET OF PLANS. |
| | |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE PLANS ARE NOT CLEAR AS TO THE FOUNDA |
| | TION, AREAL PHOTOS INDICATE AN EXISTING |
| | SLAB. IS THIS SLAB TO BE REMOVED? IF NOT |
| | THIS SLAB HAS TO BE CERTIFIED BY THE |
| | ENGINEER THAT IT WILL ACCEPT THE LOADS |
| | BEING IMPOSED ON IT! |
| | |
| | 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | SOILS REPORT SIGNED/ SEALED BY SOILS |
| | ENGINEER. |
| | |
| | 4) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 5)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | IF COUNTY IMPACT FEES WERE PAID UNDER |
| | THE OLD CANCEALED PERMIT, THE PLANS |
| | STILL NEED TO SUBMITTED TO THE COUNTY |
| | FOR REVIEW AND STAMPING! |
| | |
| | 6)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 7) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 8)1005.4 EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS, |
| | (2) EVERY ROOM OR SPACE GREATER THAN |
| | 250 FT USED FOR CLASSROOM OR OTHER ED- |
| | UCATIONAL PURPOSES OR NORMALLY SUBJECT |
| | TO STUDENT OCCUPANCY, AND EVERY ROOM |
| | SUBJECT TO CLIENT OCCUPNCY SHALL NOT |
| | HAVE NOT LESS THAN ONE OUTSIDE WINDOW |
| | FOR EMERGENCY RESCUE, SEE EXCEPTIONSALSO |
| | EXCEPTION #1 AN AUTOMATIC FIRE |
| | SPRINKLER SYSTEM, PLANS INDICATE THERE |
| | SHALL BE ONE, BUT NO PLANS WERE SUBMIT- |
| | TED? |
| | |
| | 9)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A-1 THE PLANS INDICATE ALOT OF THE |
| | 3'-0" DOORS BEING DRAWN IN AS A 2'-0" |
| | DOOR, THIS MAY CAUSE PROBLEMS WITH THE |
| | REQUIRED MANEUVERING CLEARENECES AT |
| | DOORS, (11-4.13.6) DOORS 27 & 42 DO NOT |
| | HAVE THE REQUIRED 18" ON THE LATCH SIDE! |
| | THE DOORWAYS DRAWN IN AS 2'-0" MAY ALSO |
| | RUN INTO THESE SAME PROBLEMS, PLEASE |
| | REVIEW? |
| | |
| | 10) ACCESSIBLE MEANS OF EGRESS, |
| | 11-4.1.3(8), (9) |
| | ALL CLASSROOMS HAVING EXTERIOR DOORS & |
| | LANDINGS SHOULD BE MADE TO BE ACCESSIBLE |
| | LANDINGS NO LOWER THAN 1/2" BELOW THE |
| | INTERIOR FINISH FLOOR. SHEET A-3 DETAIL |
| | 11/A5 A CUT SECTION THRU A EXTERIOR DOOR |
| | AND STOOP. STOOP ELEVATION MISSING FROM |
| | THE CUT SECTION? SHEET A-10 NOTES: INDIC |
| | ATE SLOPED SIDEWALKS TO MEET ADA GUIDE- |
| | LINES, THIS SHOULD ALSO INCLUDE THE |
| | EXTERIOR DOOR LANDINGS. LANDINGS NEED TO |
| | BE BIG ENOUGH FOR TURNING RADIUS, AND |
| | THE DRADE NEEDS TO BE TO THE TOP OF THE |
| | LANDING FOR ACCESSIBILITY, WITH POSITIVE |
| | SLOPE AWAY FROM THE BUILDING. |
| | |
| | 11) BUILDING SIGNAGE: 11-4.1.3(16)(A)(B) |
| | SIGNS WHICH DESIGNATE PERMANENT ROOMS & |
| | SPACESSHALL COMPLY WITH 11-4.30.1, |
| | 11-4.30.4, 11-4.30.(5-6). |
| | B) OTHER SIGNS WHICH PROVIDE DIRECTION |
| | TO OR INFORMATION ABOUT FUNCTION SPACES |
| | OF THE BUILDING SHALL COMPLY WITH: |
| | 11-4.30.1, 11-4.30.2, 11-4-30.3 & 11-4.5 |
| | |
| | 12) PROVIDE INFORMATION FOR AN ACCESS- |
| | IBLE DINING ROOM 11.5.4. |
| | |
| | 13) 11-4.1.2 VERTICAL ACCESSIBILITY, |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. |
| | PROVIDE INFORMATION FOR VERTICAL |
| | LIFT ONTO THE STAGE. |
| | |
| | 14)11-4.22.2 DOORS. ALL DOORS TO |
| | ACCESSIBLE TOLIET ROOMS SHALL COMPLY |
| | WITH 11-4.13. DOORS SHALL NOT SWING INTO |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY |
| | FIXTURE. |
| | ROOM # 35 GIRLS HANDICAPPED STALL OVER |
| | LAPPING DOOR SWING INTO CLEARTHE CLEAR |
| | FLOOR SPACE. |
| | |
| | 15) 1021.4(NEW UNDER 2001 FBC) DOORS |
| | THAT SWING INTO AN EXIT ACCESS CORRIDOR |
| | SHALL BE RECESSED TO PREVENT INTERFE- |
| | ENCE WITH CORRIDOR TRAFFIC: ANY DOORS |
| | NOT RECESSED SHALL OPEN 180 DEGREES TO |
| | STOP AGAINST THE WALL. DOORS IN ANY POSI |
| | TION SHALL NOT REDUCE THE REGUIRED CORRI |
| | DOR WIDTH BY MORE THAN ONE HALF. |
| | |
| | 16) REQUIRED CORRECTIONS: |
| | A) TITLE SHEET 2002 FLORIDA BUILDING |
| | CODE |
| | B) SHEET A-5, REFRENCE TO STANDARD |
| | BUILDING CODE |
| | C) SHEET A-5 BASIC WIND VELOCITY 110 |
| | |
| | 17)COVER SHEET MISSING : |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | MISSING # (4) INTERNAL PRESSURE COEF. |
| | |
| | NOTE: PLAN REWIEW ALLOWS FOR 200 |
| | LINES, ANOTHER"BUILDING PLAN REVIEW" |
| | WILL NEED TO BE OPENED TO CONTINUE |
| | COMMENTS. |