| 2003-06-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03031179 |
| | ADD: 4200 BEAR LAKES COURT |
| | CONT: ALLIANCE |
| | TEL: (305)345-2029 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE 3 COPIES OF SOILS REPORT. |
| | |
| | 3) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORTS: |
| | |
| | A) WINDOWS, FIXED & SINGLE HUNG |
| | B) DOORS (6 PANEL) DOORS |
| | C) ROOF ASSEMBLIES |
| | D) STORM SHUTTER KEY PLAN/ ANCHOR |
| | INSTALLATION SCHEDULE |
| | |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. SEE SAMPLE ATTACHED! |
| | |
| | BE SURE TO TAKE THE VALUES FOR MASONARY |
| | NOT 3000 PSI CONCRETE FOR ANCHOR SPACING |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |