2003-06-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031179
 ADD: 4200 BEAR LAKES COURT
 CONT: ALLIANCE
 TEL: (305)345-2029
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE 3 COPIES OF SOILS REPORT.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
  
 A) WINDOWS, FIXED & SINGLE HUNG
 B) DOORS (6 PANEL) DOORS
 C) ROOF ASSEMBLIES
 D) STORM SHUTTER KEY PLAN/ ANCHOR
 INSTALLATION SCHEDULE
  
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. SEE SAMPLE ATTACHED!
  
 BE SURE TO TAKE THE VALUES FOR MASONARY
 NOT 3000 PSI CONCRETE FOR ANCHOR SPACING
  
 BUILDING PLAN REVIEW