Plan Review Notes
Plan Review Notes For Permit 03031179
Permit Number 03031179
Review Stop P
Sequence Number 1
Notes
Date Text
2003-04-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT PM-1 SECTION 1503.4.4 (BLDG CODE)
 CONDENSATE SHALL DRAIN MINIMUM 1' AWAY
 FROM THE STRUCTURE SIDEWALL.
 2) SHTS PM-1/PM-2 FLOOR DRAIN NOT AN
 APPROVED INDIRECT WASTE. FLOOR SINK IS
 REQUIRED FOR INDIRECT WASTE FROM THE ICE
 MACHINE. SECTION 802.3
 3) SHTS PM-1/PM-2 THE RELIEF VALVE DIS-
 CHARGE PIPING SHALL NOT HAVE ANY TRAPPED
 SECTIONS. SECTION 504.7.1
 4) SHT PM-2 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION
 607.3.2 (EXPANSION TANK REQUIRED)
 5) SHT PM-2 WATER HEATER DETAIL, EMER-
 GENCY PAN NOT SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377