| Plan Review Notes For Permit 03031179 |
| Permit Number |
03031179 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT PM-1 SECTION 1503.4.4 (BLDG CODE) | | | CONDENSATE SHALL DRAIN MINIMUM 1' AWAY | | | FROM THE STRUCTURE SIDEWALL. | | | 2) SHTS PM-1/PM-2 FLOOR DRAIN NOT AN | | | APPROVED INDIRECT WASTE. FLOOR SINK IS | | | REQUIRED FOR INDIRECT WASTE FROM THE ICE | | | MACHINE. SECTION 802.3 | | | 3) SHTS PM-1/PM-2 THE RELIEF VALVE DIS- | | | CHARGE PIPING SHALL NOT HAVE ANY TRAPPED | | | SECTIONS. SECTION 504.7.1 | | | 4) SHT PM-2 WATER HEATER DETAIL, THERMAL | | | EXPANSION CONTROL IS REQUIRED. SECTION | | | 607.3.2 (EXPANSION TANK REQUIRED) | | | 5) SHT PM-2 WATER HEATER DETAIL, EMER- | | | GENCY PAN NOT SHOWN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|