| Plan Review Notes For Permit 03031179 |
| Permit Number |
03031179 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-03 00:00:00 | DENIED: PLANS DATED 3-5-03 | | | | | | 1.PLEASE CLARIFY THE ENERGY GAUGE FORM | | | 4001-2001.FORM INDICATES MAX TONNAGE | | | AS 2.THE SIZING SUMMARIES AND PLANS | | | SHOW FOUR SPLIT SYSTEMS THAT TOTAL MORE | | | THAN 2 TONS.PLEASE CORRELATE. | | | | | | 2.RETURN AIR REQUIRED FROM THE BILLARD | | | ROOM & EXERCISE RM.2001 FBC(M) 601.4 | | | | | | 3.SEE COMMENT BY K. STEVENS (PLUMBING) | | | ON CONDENSATE TERMINATION, 1 FT MINIMUM | | | FROM BUILDING STRUCTURE AS PER 2001 FBC | | | 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|