 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM SHOWS A METER AND
 ASEPARATE DISCONNECT. THE PLAN
 INDICATES A METER MAIN COMBINATION,
 PLEASE
 CLARIFY.
  
 2} THE FEED FROM THE DISCONNECT (IF
 THERE IS ONE) TO THE PANEL NEEDS A
 GROUND PER 250.122.
  
 3} THE KITCHEN RECEPTACLE CIRCUITS MUST
 COMPLY WITH 210.11(C)(1). THERE MUST BE
 A MINIMUM OF 2@1500 VA, AND THE LIVING
 ROOM MAY NOT BE ON EITHER CIRCUIT. SEE
 210.52(B) FOR WHAT IS ALLOWED. PLEASE
 MAKE NECESSARY CHANGES TO THE PANEL
 SCHEDULE.
  
 4} THE LAUNDRY CIRCUITS MUST COMPLY
 WITH220.16(B). THIS CIRCUIT WAS REMOVED
 FROM THE SCHEDULE. IF USING THE LABEL
 "WASHER" TO INDICATE THE LAUNDRY
 CIRCUIT IT MUST BE CALCULATED @ 1500VA.
  
 5} THE BATH GFI MUST COMPLY WITH 210.11
 (C)(3), 20 AMP, # 12.SEE SCHEDULE LISTS
 SAME AT 15 AMP #14.
  
 6} PLEASE SEE THAT ALL KITCHEN
 COUNTERTOP RECEPTACLES MUST COMPLY WITH
 210.11(C)(1), 210.8(A)(6), AND
 210.52(C).
  
 7} PLEASE SEE CIRCUIT #20, SHED? REFER
 ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  