| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE RISER DIAGRAM SHOWS A METER AND |
| | ASEPARATE DISCONNECT. THE PLAN |
| | INDICATES A METER MAIN COMBINATION, |
| | PLEASE |
| | CLARIFY. |
| | |
| | 2} THE FEED FROM THE DISCONNECT (IF |
| | THERE IS ONE) TO THE PANEL NEEDS A |
| | GROUND PER 250.122. |
| | |
| | 3} THE KITCHEN RECEPTACLE CIRCUITS MUST |
| | COMPLY WITH 210.11(C)(1). THERE MUST BE |
| | A MINIMUM OF 2@1500 VA, AND THE LIVING |
| | ROOM MAY NOT BE ON EITHER CIRCUIT. SEE |
| | 210.52(B) FOR WHAT IS ALLOWED. PLEASE |
| | MAKE NECESSARY CHANGES TO THE PANEL |
| | SCHEDULE. |
| | |
| | 4} THE LAUNDRY CIRCUITS MUST COMPLY |
| | WITH220.16(B). THIS CIRCUIT WAS REMOVED |
| | FROM THE SCHEDULE. IF USING THE LABEL |
| | "WASHER" TO INDICATE THE LAUNDRY |
| | CIRCUIT IT MUST BE CALCULATED @ 1500VA. |
| | |
| | 5} THE BATH GFI MUST COMPLY WITH 210.11 |
| | (C)(3), 20 AMP, # 12.SEE SCHEDULE LISTS |
| | SAME AT 15 AMP #14. |
| | |
| | 6} PLEASE SEE THAT ALL KITCHEN |
| | COUNTERTOP RECEPTACLES MUST COMPLY WITH |
| | 210.11(C)(1), 210.8(A)(6), AND |
| | 210.52(C). |
| | |
| | 7} PLEASE SEE CIRCUIT #20, SHED? REFER |
| | ON PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |