2003-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. SECTION 909.1
 THE WASH MACHINE SHALL CONNECT DOWN-
 STREAM OF THE BATHROOM GROUP.
 2) SHT 4 0F 4 SHOWER LABLED SINK, AND
 MINIMUM SIZE OF PIPE UNDER SLAB AND FOR
 SHOWER IS 2". 1-1/4" SHOWN.
 3) SHT 4 OF 4 NOTE #1 CODE SHALL READ
 FBC-2001 PLUMBING, NOT NATIONAL PLUMBING
 CODE.
  