| 2003-03-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE SERVICE IS TO SMALL FOR | | | FOR THE ADDITIONAL LOAD. | | | SUBMIT A RISER DIAGRAM WITH FEEDER SIZES | | | AND GROUNDING DETAILS.SEE 215-5. | | | | | | THE LAUNDRY CIRCUIT IS REQUIRED TO BE 20 | | | AMP PER 210-11(C)(2). | | | | | | THE GARAGE NEEDS A GFI PER 210-8(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 |
|