| Date |
Text |
| 2003-07-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | FOLLOWING COMMENTS NOT ADDRESSED FROM |
| | PREVIOUS REVIEW. FOR CLAIRTY THE COMMENT |
| | NUMBER FROM FIRST REVIEW WILL BE USED. |
| | |
| | 4) SHT P-1 #13 FILTER SHALL COMPLY WITH |
| | NSF STANDARD. MANUF. INFO REQUIRED. - |
| | INFORMATION RECIEVED AND NSF LISTING NOT |
| | SHOWN. CHECKED NSF RECORDS AND NO LIST- |
| | ING SHOWN FOR THIS PRODUCT. SEC 303.4 |
| | 7) (IN PART) WATER HAMMER ARRESTORS REQ- |
| | UIRED BY SEC 406.9 SHALL BE LOCATED NEAR |
| | THE FIXTURE IN AN "EFFECTIVE RANGE", NOT |
| | IN THE CEILING AT THE TOP OF THE DROP. |
| | PDI-WH 201 AND MANUFACTURE INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | NEW COMMENT: SEE ATTACHED SHEET CONCERN- |
| | ING FLORIDA STATUTE 553.80(2)(B) |
| | |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |