| Plan Review Notes For Permit 03031105 |
| Permit Number |
03031105 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-30 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING COMMENTS FROM | | | THE LAST REVIEW THAT WERE ONLY | | | PARTIALLY ADDRESSED OR NOT | | | SATIFACTORILY ADDRESSED. | | | | | | 1} THE PANEL SCHEDULES ARE STILL LISTING | | | MLO & MAIN,AND NOW PANELS "C" & "P" | | | LIST MCB.IF THE PANEL RATING IN AMPS IS | | | 225 OR 100,IT SHOULD NOT BE LISTED AS | | | IF THAT WERE THE MAIN BREAKER | | | SIZE.PLEASE CLARIFY ALL PANEL | | | DESIGNATIONS WITH CONSISTENCY. | | | | | | 2} THERE ARE STILL SEVERAL EXIT & | | | EMERGENCY LIGHTS ON CIRCUIT A-20(SHEET | | | E-2). THIS IS IN VIOLATION OF ARTICLE | | | 700-12(E). | | | | | | PLEASE CORRECT AND RESUBMIT FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|