| 2003-03-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A2.2 PROVIDE CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SEC'S 1106 & 1107. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS, (1106.4), INCLUDING |
| | PARAPET, (1106.5). SHOW AREA OF ROOFS |
| | THAT DRAIN ON TO ROOF FROM ABOVE. |
| | INDICATE SQUARE FOOTAGE DRAINED BY EACH. |
| | 2) SHT 2.2 INDICATE PITCH OF GUTTERS PER |
| | TABLE 1106.6 AND SHOW SQUARE FOOTAGE |
| | DRAINED FROM EACH ROOF AREA TO GUTTER. |
| | 3) SHT A2.2 INDICATES 24"X16" SCUPPERS |
| | AND OVERFLOW SCUPPERS. IT SAYS TYPICAL |
| | OF 5, BUT ONLY 4 ARE SHOWN. PLEASE |
| | CLAIRFY. |
| | 4) SHT P-1 #13 FILTER SHALL COMPLY WITH |
| | NSF STANDARD. MANUF. INFO. REQUIRED. |
| | 5) SHT P-1 #'S 15 & 19, FLOOR DRAINS ARE |
| | NOT APPROVED FOR INDIRECT WASTE. ALL |
| | INDIRECT WASTE SHALL DRAIN TO FLOOR SINK |
| | SECTION 802.3 |
| | 6) SHT P-3 DETAILS #3 & 6, FLOOR SINKS |
| | REQUIRED. SECTION 802.3 |
| | 7) SHT P-4 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED. WATER HAMMER |
| | ARRESTORS REQUIRED BY 406.9, (AT QUICK |
| | CLOSING VALVES), SHALL BE LOCATED NEAR |
| | THE FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| | AT THE TOP OF THE DROP IN THE CEILING. |
| | PDI-WH 201 & MANUF. INSTALLATION INSTR. |
| | 8) IRRIGATION PERMIT REQUIRED. PLUMBING |
| | CONTRACTOR SHALL TIE INTO WATER SERVICE |
| | AND SUPPLY SHUT OFF VALVE FOR IRRIGATION |
| | |
| | REVIEW BY KEN STEVENS |