| Plan Review Notes For Permit 03031105 |
| Permit Number |
03031105 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-24 00:00:00 | ************* UNSAT ******************** | | | | | | | | | 1)NOTE: PLEASE SEE GENERAL NOTE FOR | | | AIC RATINGS. IT IS NOTED THAT "PANELS" | | | ARE TO BE 65K SERIES RATED, PLEASE | | | CLARIFY IF THIS IF FOR MAIN DISC ALSO.? | | | 110-9 | | | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND PANEL SCHEDULES. PLEASE SEE RISER | | | SHOWS PANELS "C" AND "P" AS 225A AND | | | PANEL SCHEDULES SHOW THEM AS 100A. | | | PLEASE ALSO CLARIFY PANELS. THEY ARE | | | ALL SHOWN AS MLO AND MCB? P RISER SHOWS | | | PANELS AS BEING MLO.? | | | | | | 3)NOTE: PLEASE SHOW CIRCUITING FOR | | | EM/EXT LTS PER 700-12E | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|