| Notes |
| Date |
Text |
| 2003-03-28 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66, BASED ON MIN SEC`S | | | FROM 310-15. | | | | | | 2)NOTE: PLEASE CORRELATE PANEL WITH | | | RISER DIAGRM. PANELS SHOWN AS 150A AND | | | RISER SHOWS AS 200A`S?? | | | | | | 3)NOTE: PLEASE SEE 220-16B FOR MIN SIZE | | | FOR WASHER CIRCUIT. | | | | | | 4)NOTE: SD NOT PERMITTED IN KITCHEN PER | | | NFPA-72 8-1.4.2 | | | | | | 5)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND PANEL "B", SIZE PER 250-122 | | | | | | 6)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) PER 210-52D/210-11-C3 | | | | | | 7)NOTE:PLEASE SHOW LOCATION OF PANEL B. | | | | | | 8)NOTE: PLAN SHOWS TWO SD`S IN MASTER | | | BEDROOM. PLEASE NOTE, TWO MAY BE | | | INSTALLED, HOWEVER AN ADDITIONAL SD | | | NEEDS TO BE OUTSIDE BR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|