2003-03-28 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66, BASED ON MIN SEC`S
 FROM 310-15.
  
 2)NOTE: PLEASE CORRELATE PANEL WITH
 RISER DIAGRM. PANELS SHOWN AS 150A AND
 RISER SHOWS AS 200A`S??
  
 3)NOTE: PLEASE SEE 220-16B FOR MIN SIZE
 FOR WASHER CIRCUIT.
  
 4)NOTE: SD NOT PERMITTED IN KITCHEN PER
 NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL "B", SIZE PER 250-122
  
 6)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11-C3
  
 7)NOTE:PLEASE SHOW LOCATION OF PANEL B.
  
 8)NOTE: PLAN SHOWS TWO SD`S IN MASTER
 BEDROOM. PLEASE NOTE, TWO MAY BE
 INSTALLED, HOWEVER AN ADDITIONAL SD
 NEEDS TO BE OUTSIDE BR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]