Plan Review Notes
Plan Review Notes For Permit 03031048
Permit Number 03031048
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-28 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66, PLEASE SEE MIN
 SEC`S PER 310-15
  
 2)NOTE: SD NOT PERMITTED IN KITCHEN,
 NFPA-72 8-1.4.2
  
 3)NOTE: PLEASE SHOW MIN SIZE FOR WASHER
 CIRCUIT 220-16B. SHOWN AS 1.0
  
 4)NOTE: PLEASE SHOW AND INDENTIFY
 LOCATION OF PANELS.
  
 PLEASE VERIFY SIZE OF SERVICE WITH
 CONTRACTOR. SHOWN AS 400A`S W/ 152A`S??
 THIS IS JUST A NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]