| Plan Review Notes For Permit 03031048 |
| Permit Number |
03031048 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-28 00:00:00 | ************ UNSAT ****************** | | | | | | 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66, PLEASE SEE MIN | | | SEC`S PER 310-15 | | | | | | 2)NOTE: SD NOT PERMITTED IN KITCHEN, | | | NFPA-72 8-1.4.2 | | | | | | 3)NOTE: PLEASE SHOW MIN SIZE FOR WASHER | | | CIRCUIT 220-16B. SHOWN AS 1.0 | | | | | | 4)NOTE: PLEASE SHOW AND INDENTIFY | | | LOCATION OF PANELS. | | | | | | PLEASE VERIFY SIZE OF SERVICE WITH | | | CONTRACTOR. SHOWN AS 400A`S W/ 152A`S?? | | | THIS IS JUST A NOTE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|