| Plan Review Notes For Permit 03031045 |
| Permit Number |
03031045 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-28 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66 AND SIZED PER SEC`S | | | PER 310-15 | | | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND PANELS. SHOWN AS 150AAND 200A?? | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL "B". SIZE PER 250-122 | | | | | | 4)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210-52C1 FOR KITCHEN COUNTERSPACE. | | | | | | 5)NOTE: PLEASE SEE MISSING REQ`D BATH | | | CIRCUIT(S) PER 210-52D/210-11-C3 | | | | | | 6)NOTE: PLEASE SEE 220-16B FOR MIN KW | | | FOR WASHER CIRCUIT. | | | | | | 7)NOTE: PLEASE SEE MASTER BEDROOM, | | | SHOWS TWO SD`S INSIDE AND NONE OUTSIDE | | | , PLEASE ADD OR MOVE SD. | | | PLEASE ALSO REMOVE SD FROM KITCHEN,\\ | | | NOT PERMITTED PER NFPA-72 8-1.4.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|