2003-03-28 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66 AND SIZED PER SEC`S
 PER 310-15
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. SHOWN AS 150AAND 200A??
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL "B". SIZE PER 250-122
  
 4)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52C1 FOR KITCHEN COUNTERSPACE.
  
 5)NOTE: PLEASE SEE MISSING REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11-C3
  
 6)NOTE: PLEASE SEE 220-16B FOR MIN KW
 FOR WASHER CIRCUIT.
  
 7)NOTE: PLEASE SEE MASTER BEDROOM,
 SHOWS TWO SD`S INSIDE AND NONE OUTSIDE
 , PLEASE ADD OR MOVE SD.
 PLEASE ALSO REMOVE SD FROM KITCHEN,\\
 NOT PERMITTED PER NFPA-72 8-1.4.2
  