| Plan Review Notes For Permit 03031042 |
| Permit Number |
03031042 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-28 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE SD IN KITCHEN, NOT | | | PERMITTED UNDER NFPA-71 8-1.4.2 | | | PLEASE ALSO SEE TWO SD`S SHOWN IN MASTER | | | BEDROOM. TWO CAN BE INSTALLED,HOWEVER | | | ANOTHER ONE WOULD NEED TO BE OUTSIDE. | | | | | | 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66, SIZE FROM SEC`S | | | UNDER 310-15 FOR 400A SERVICE. | | | | | | 3)NOTE: PLEASE CORRELATE PANELS AND | | | RISER DIAGRAM. SHOWN AS 200A PANELS | | | ON RISER AND 150A ON SCHEDULES?? | | | | | | 4)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING COND. BETWEEN MAIN DSIC AND | | | PANEL B. SIZE PER 250-122. | | | | | | 5)NOTE: PLEASE ADD RECEPT ALONG KITCHEN | | | COUNTERSPACE PER 210-52C-1 | | | | | | 6)NOTE: PLEASE SEE WASHER KW, SIZE PER | | | MIN 220-16B. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] | | | | | | 7)NOTE: PLEASE LIST MISSING REQ`D BATH | | | CIRCUIT(S) PER 210-52D/210-11C-3 |
|