Date Text
2003-03-28 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE SD IN KITCHEN, NOT
 PERMITTED UNDER NFPA-71 8-1.4.2
 PLEASE ALSO SEE TWO SD`S SHOWN IN MASTER
 BEDROOM. TWO CAN BE INSTALLED,HOWEVER
 ANOTHER ONE WOULD NEED TO BE OUTSIDE.
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66, SIZE FROM SEC`S
 UNDER 310-15 FOR 400A SERVICE.
  
 3)NOTE: PLEASE CORRELATE PANELS AND
 RISER DIAGRAM. SHOWN AS 200A PANELS
 ON RISER AND 150A ON SCHEDULES??
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING COND. BETWEEN MAIN DSIC AND
 PANEL B. SIZE PER 250-122.
  
 5)NOTE: PLEASE ADD RECEPT ALONG KITCHEN
 COUNTERSPACE PER 210-52C-1
  
 6)NOTE: PLEASE SEE WASHER KW, SIZE PER
 MIN 220-16B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
  
 7)NOTE: PLEASE LIST MISSING REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11C-3