| 2003-04-04 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)PROVIDE A SOIL BORING TEST AS REQUIRED |
| | BY FBC 1804.2.2. |
| | |
| | 4) GENERAL NOTE #1 ON C1 LISTS THE WRONG |
| | CONSTRUCTION TYPE. SHOULD BE TYPE VI. |
| | |
| | 5) INDICATE THE INTERNAL PRESSURE |
| | COEFFICENT PER FBC 1606.1.7. |
| | |
| | 6) SPECIFY ON THE PLANS THAT THE SPACING |
| | OF THE INTERMEDIATE RAILS FOR THE |
| | BALCONY GUARDRAIL SHALL REJECT THE |
| | PASSAGE OF A 4" SPHERE AND THE BOTTOM |
| | RAIL SHALL REJECT A 2" SPHERE. |
| | |
| | 7)SPECIFY ON THE PLANS THAT FIREBLOCKING |
| | IS REQUIRED AT THE CONCEALED SPACES |
| | BETWEEN THE STAIR STRINGERS AT THE TOP |
| | AND BOTTOM OF THE RUNS. FBC 2305.1.4. |
| | |
| | 8) THE VALUES IN TRUSS CONNECTION |
| | SCHEDULE ARE INCORRECT. DOUBLING THE |
| | STRAPS DOES NOT DOUBLE THE LOAD VALUES. |
| | SEE THE ATTACHED COPIES FROM 2003 USP |
| | CATALOG. |
| | |
| | 9) PROVIDE MANUFACTURER'S SPECIFICATIONS |
| | AND UL LISTING INFORMATION FOR THE ONE |
| | HOUR FIRE RATED WECK GLASS BLOCK. |
| | |
| | 10) SUBMIT PRODUCT APPRVALS FOR THE 16' |
| | WIDE GARAGE DOOR. |
| | |
| | 11) THE SIZE OF THE GLASS BLOCK OPENING |
| | IN THE WINDOW SCHEDULE ON SHEET A2 DOES |
| | NOT CORRESPOND TO THE SIZE LISTED ON THE |
| | PLANS. PLEASE CORRECT. |
| | |
| | 12) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS ARE |
| | MISSING TWO (2) OF THE OPENINGS ON THE |
| | FIRST FLOOR. (THE DINING ROOM WINDOWS & |
| | A WINDOW ON THE LEFT ELEVATION) THE |
| | WRONG SIZES ARE GIVEN FOR THE WINDOWS ON |
| | THE LEFT ELEVATION. PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |