Plan Review Notes
Plan Review Notes For Permit 03031040
Permit Number 03031040
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-07 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO THE
 PLAN FOR CODE COMPLIANCE.
  
 1} THE #4 GROUNDING CONDUCTOR ELECTRODE
 CONDUCTOR IS INCORRECT FOR THE 400 AMP S
 ERVICE SHOWN.
  
 2} PLEASE SHOW PANEL "B" LOCATION ON PLA
 N AND SUBMIT A PANEL SCHEDULE FOR SAME.
  
 3} THE LAUNDRY CIRCUIT NAAEDS TO COMPLY
 WITH 220-16(B) IN THE LOED CALCS.
  
 4} THE SMOKE DETECTOR CANNOT BE LOCATED
 IN THE KITCHEN,MUST COMPLY WITH 8-1.4.2,
 NFPA-72.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392