| Plan Review Notes For Permit 03031040 |
| Permit Number |
03031040 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-07 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO THE | | | PLAN FOR CODE COMPLIANCE. | | | | | | 1} THE #4 GROUNDING CONDUCTOR ELECTRODE | | | CONDUCTOR IS INCORRECT FOR THE 400 AMP S | | | ERVICE SHOWN. | | | | | | 2} PLEASE SHOW PANEL "B" LOCATION ON PLA | | | N AND SUBMIT A PANEL SCHEDULE FOR SAME. | | | | | | 3} THE LAUNDRY CIRCUIT NAAEDS TO COMPLY | | | WITH 220-16(B) IN THE LOED CALCS. | | | | | | 4} THE SMOKE DETECTOR CANNOT BE LOCATED | | | IN THE KITCHEN,MUST COMPLY WITH 8-1.4.2, | | | NFPA-72. | | | | | | 5} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|