Plan Review Notes For Permit 03031022
Permit Number 03031022
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND MAKE NECESARRY CHANES ON THE PLANS.
  
 1} INDICATE HOW THE NEW STRUCTURE IS BEI
 NG FED.SHOW THE LOCATION OF THE DISCONNE
 CT FOR COMPLIANCE WITH 225-31,32 & 250-3
 2.
  
 2} PROVIDE LOAD CALCULATIONS PER 215-5,
 ALSO GIVE SIZE OF EXISTING SERVICE.
  
 3} PROVIDE A PANEL SCHEDULE SHOWING COMP
 LIANCE WITH 210-11(C)(3) & 210-12.
  
 4} PLEASE SHOW A SMOKE DETECTOR TO COMPL
 Y WITH NFPA-72,8-1.4.1.6.2(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392