| Plan Review Notes For Permit 03031005 |
| Permit Number |
03031005 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-03 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE CORRECT INFORMATION FOR STORM | | | SHUTTERS. SEE ENGINEERED DRAWINGS AND | | | REVISE THE INSTALLATION SCHEDULE | | | SUBMITTED FOR THIS PROJECT. CHECK THE | | | DESIGN PRESSURES, PANEL SPAN & ANCHOR | | | TYPE AND SPACING. | | | 2-REVISE DETAIL S-21 FOR COLUMN LOCATED | | | BETWEEN GARAGE AND STAIRWAY. DETAIL | | | SHOWN DOESN'T APPLY.SEC. 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 3-SHEET S-1: REVISE CONNECTOR TC-1 SHOWN | | | ON ROOF PLAN AT SECOND FLOOR FRONT | | | ELEVATION. NEED WOOD TO SPECIFY WOOD | | | TO WOOD CONNECTOR. SEC. 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 4-34SH WINDOW DON'T ALLOW THE 24" CLEAR | | | HEIGHT OPENING. REVISE AS REQUIRED. | | | ALSO CHECK THAT 24+5SH WINDOW PROVIDES | | | 5.7 SF CLEAR OPENING. AS REQUIRED BY | | | SEC. 1005.4.4 FBC 2001. | | | 5-ENERGY CALCULATIONS TO HAVE ENGINEER'S | | | ORIGINAL SIGNATURE AND DATE AS REQ'D | | | BY CHAPTER 471 FLORIDA STATUTES AND | | | SEC. 103.0 CHAPTER 13 OF FBC 2001. |
|