| Plan Review Notes For Permit 03031002 |
| Permit Number |
03031002 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-05 00:00:00 | PROVISO: | | | | | | 1.PROVIDE OUTSIDE AIR CALCS AS PER | | | 2001 FBC(M) 402.2 (NATURAL) OR TABLE | | | 403.3, ON JOBSITE FOR ROUGH INSPECTION. | | | | | | 2.CLARIFY ENERGY & MANUAL J CALCS ON | | | SIZING OF A/C EQUIPMENT INDICATES A 4 | | | TON UNIT AND PLAN SCHEDULE ON PLAN SHEET | | | M-1 SHOW A 5 TON UNIT. | | | | | | 3.FAN SHUTDOWN REQUIRED AT FINAL | | | INSPECTION AS PER 2001 FBC(M) 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|