| Plan Review Notes For Permit 03030999 |
| Permit Number |
03030999 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-26 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE CORRECT THE PLANS TO COMPLY WITH | | | THE FOLLOWING. | | | | | | 1} THE FEEDER FROM THE MAIN TO PANEL "A" | | | IS INCORRECT FOR 200 AMPS. | | | | | | 2} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 3} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 4} PLEASE NOTE THAT THE RECEPTACLE | | | SPACING IN THE DINING ROOM DOES NOT | | | COMPLY WITH 210-52(A)(1). | | | | | | 5} SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | IN THE VICINITY OF BEDROOMS AND CLOSE | | | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 | | | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|