| Plan Review Notes For Permit 03030869 |
| Permit Number |
03030869 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-07 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE UPDATED SBCCI REPORT #2229A | | | WHICH IS THE ONE THAT MATCHES THE | | | ENGINEERED DRAWINGS FOR STORM SHUTTERS | | | 2-DETAIL S21 FOR COLUMN BETWEEN GARAGE & | | | STAIRWAY DOESN'T. REVISE AS REQUIRED. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 3-RE-SUBMIT ENERGY CALCULATIONS WITH | | | ENGINEER'S ORIGINAL SIGNATURE AND | | | SEAL AS REQUIRED BY CHAPTER 471 FL. | | | STATUTES AND SEC. 103.0 OF CHAPTER | | | 13 FBC 2001. |
|