| Plan Review Notes For Permit 03030857 |
| Permit Number |
03030857 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE UPDATED SBCCI REPORT #2229A | | | THAT MATCHES ENGINEERED DRAWINGS FOR | | | STORM SHUTTERS. | | | ALSO, REVISE THE DESIGN PRESSURES | | | SHOWN ON INSTALLATION SCHEDULE. SEE | | | ENGINEERED DWGS FOR MAX./MIN. PANEL | | | SPAN AND ANCHOR SPACING ACCORDING TO | | | THE DESIGN PRESSURES. | | | 2-REVISE DETAIL S21 FOR COLUMN LOCATED | | | BETWEEN GARAGE AND STAIRWAY. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 3-RE-SUBMIT ENERGY CALCULATIONS WITH | | | ENGINEER'S ORIGINAL SIGNATURE & SEAL. | | | CHAPTER 471 FLORIDA STATUTES AND SEC. | | | 103.0 CHAPTER 13 FBC 2001. |
|