| Plan Review Notes For Permit 03030808 |
| Permit Number |
03030808 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-09 00:00:00 | ********** NOTES REDLINED ******** | | | | | | | | | | | | | | | | | | 1)NOTE: PLEASE SEE 210-52D/ 210-11C-3 | | | FOR MISSING BATH RECEPT. MUST BE 20A AND | | | #12. | | | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED BEDROOM CIRCUIT PER 210-12 | | | | | | 3)NOTE: PLEASE CLARIFY MISSING REAR | | | RECEPT PER 210-52E | | | | | | PLEASE SEE PLANS FOR NOTES. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT |
|