 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE NOTE ON SHEET "A2" INDICATES
 THERE WILL BE WORK DONE ON THE
 SERVICE.PLEASE PROVIDE AIC RATINGS PER
 110-9 & 110-10.ALSO CORRECTED PANEL
 SCHEDULES,LOAD CALC'S.,AND RISER DIAGRAM
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} THE SMALL APPLIANCE CIRCUITS ON THE
 LOAD CALCULATION (2@ 1500 VA) AND THE
 PANEL SCHEDULE (3@ 1500 VA) DO NOT
 CORRESPOND,PLEASE CORRECT SAME.
  
 4} THE DRYER ON THEPANEL SCHEDULE AND
 THE LOAD CALCS IS LISTED AT DIFFERENT
 VALUES. SEE 220-16(B).
  
 5} THE BATH UPSTAIRS NEEDS A RECEPTACLE
 PER 210-52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  