| Plan Review Notes For Permit 03030747 |
| Permit Number |
03030747 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-06 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | TO THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} THE NOTE ON SHEET "A2" INDICATES | | | THERE WILL BE WORK DONE ON THE | | | SERVICE.PLEASE PROVIDE AIC RATINGS PER | | | 110-9 & 110-10.ALSO CORRECTED PANEL | | | SCHEDULES,LOAD CALC'S.,AND RISER DIAGRAM | | | | | | 2} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 3} THE SMALL APPLIANCE CIRCUITS ON THE | | | LOAD CALCULATION (2@ 1500 VA) AND THE | | | PANEL SCHEDULE (3@ 1500 VA) DO NOT | | | CORRESPOND,PLEASE CORRECT SAME. | | | | | | 4} THE DRYER ON THEPANEL SCHEDULE AND | | | THE LOAD CALCS IS LISTED AT DIFFERENT | | | VALUES. SEE 220-16(B). | | | | | | 5} THE BATH UPSTAIRS NEEDS A RECEPTACLE | | | PER 210-52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|