Plan Review Notes
Plan Review Notes For Permit 03030747
Permit Number 03030747
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 0N THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT A PANEL SCHEDULE
 SH0WING COMPLIANCE WITH THE FOLLOWING
 APPLICABLE ARTICLES.
  
 A)210-11(C)(3),BATHS.
 B)210-12,BEDROOMS.
 C)220-16(A),SMALL APPLIANCE CIRCUITS.
 D)220-16(B),LAUNDRY.
  
 2} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 3} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} PLEASE INDICATE SIZE OF EXISTING
 SERVICE.SUBMIT RISER DIAGRAM AND LOAD
 CALCS IF SERVICE IS TO BE CHANGED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 805-6718