| Plan Review Notes For Permit 03030747 |
| Permit Number |
03030747 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-25 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | 0N THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT A PANEL SCHEDULE | | | SH0WING COMPLIANCE WITH THE FOLLOWING | | | APPLICABLE ARTICLES. | | | | | | A)210-11(C)(3),BATHS. | | | B)210-12,BEDROOMS. | | | C)220-16(A),SMALL APPLIANCE CIRCUITS. | | | D)220-16(B),LAUNDRY. | | | | | | 2} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 3} SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | IN THE VICINITY OF BEDROOMS AND CLOSE | | | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 | | | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 | | | | | | 4} PLEASE INDICATE SIZE OF EXISTING | | | SERVICE.SUBMIT RISER DIAGRAM AND LOAD | | | CALCS IF SERVICE IS TO BE CHANGED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 805-6718 |
|