| 2003-04-07 00:00:00 | **********CORRECTIONS************ |
| | |
| | 1.)ENERGY CALCS REQUIRED PER FBC |
| | 13-101.2.2 AND 13-101.2.3.ENERGY CALCS |
| | SHALL INCLUDE ENTIRE HOUSE AS PER |
| | DEFINITION OF "RENOVATION" IN THE ENERGY |
| | CODE. |
| | |
| | 2.)ON THE WALL SCHEDULE, SHEET A2, |
| | STUCCO OVER METAL PLASTER BASE TO BE |
| | NOMINAL THICKNESS OF 7/8" PER |
| | FBC 2504.2.1 AND ASTM C926.ALSO |
| | SPECIFY THE WALL SHEATHING ATTACHMENT. |
| | |
| | 3.)ADDITIONAL FEES DUE.THIS CAN BE |
| | PAID WHEN THE PERMIT IS ISSUED. |
| | |
| | 4.)BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE ACTUAL PERMIT PLANS |
| | MUST BE STAMPED BY THAT OFFICE, AND A |
| | COPY OF THE PAID RECEIPT ATTACHED TO |
| | THE PERMIT APPLICATION.PLEASE CALL |
| | (561) 233-5025 FOR MORE INFORMATION. |
| | THIS CAN BE DONE AFTER PLAN REVIEW BUT |
| | MUST BE DONE BEFORE THE PERMIT CAN BE |
| | ISSUED. |
| | |
| | 5.)BEDROOM WINDOWS ARE TO COMPLY WITH |
| | EGRESS REQUIREMENTS AS PER FBC 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR. |
| | PLEASE INDICATE BEDROOM EGRESS WINDOWS, |
| | EITHER ON THE FLOOR PLAN OR ON A WINDOW |
| | SCHEDULE, GIVING WINDOW SIZES. |
| | |
| | 6.)NOTE #10, CONCRETE NOTES, SHEET C1 |
| | PER FBC 1814.3.3, DAMPPROOFING IS |
| | REQUIRED TO BE A MINIMUM OF 6 MIL. |
| | |
| | 7.)ITEM #13, ELECTRICAL NOTES REFERS |
| | TO DOOR CHIMES (POOL) AND SMOKE |
| | DETECTORS, BUT ARE NOT SHOWN ON THE |
| | ELECTRICAL PLAN.SMOKE DETECTORS ARE |
| | REQUIRED. |
| | |
| | 8.)THE PRODUCT APPROVALS FOR THE |
| | FOLLOWING ITEMS ARE EXPIRED: |
| | FRENCH DOOR |
| | ROOF TILE |
| | HURRICANE SHUTTERS |
| | PLEASE SUBMIT 2 CURRENT COPIES OF EACH. |
| | |
| | 9.)PLEASE SUPPLY PRODUCT APPROVALS FOR |
| | THE FOLLOWING ITEMS, 2 COPIES EACH: |
| | CASEMENT WINDOWS |
| | MULLIONS |
| | |
| | NOTE - PLEASE CHECK THAT THE PRODUCT |
| | APPROVALS FOR THE CASEMENT WINDOWS |
| | ARE FOR AN ARCHED WINDOW, NOT ONLY FOR |
| | A RECTANGULAR ONE. |
| | |
| | 10.)PLEASE GIVE DIMENSIONS OF |
| | INDIVIDUAL WINDOWS IN UNITS D AND E. |
| | |
| | 11.) SECOND FLOOR BEDROOM EGRESS WINDOWS |
| | ARE REQUIRED TO BE EITHER IMPACT GLASS |
| | OR TO HAVE HURRICANE SHUTTERS WHICH CAN |
| | BE REMOVED FROM THE INSIDE. |
| | |
| | 12.)A HOT WATER HEATER IS NOT SHOWN |
| | ON THE PROPOSED FLOOR PLANS.PLEASE |
| | REVISE. |
| | |
| | 13.)PROVIDE A ROOF SHEATHING NAILING |
| | SCHEDULE.PLEASE NOTE CITY AMENDMENT |
| | REVISED TABLE 2306.1. |
| | |
| | 14.)ANY CHANGES MADE TO A PLAN SEALED |
| | BY AN ARCHITECT OR ENGINEER MUST BE |
| | INITIALED BY THE INDIVIDUAL WHO SEALED |
| | THE PLAN. |
| | |
| | 15.) 1503.4 ROOF DRAINS UNLESS ROOFS ARE |
| | SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF |
| | DRAINS SHALL BE INSTALLED AT THE LOWEST |
| | POINT OF THE ROOF. WHERE REQUIRED FOR |
| | ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED |
| | AS DETERMINED BY THE ROOF SLOPE AND CON- |
| | TRIBUTING ROOF AREA. |
| | |
| | 16.) 1503.4.2 OVERFLOW DRAINS SHALL BE |
| | THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2" |
| | ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| | OR PARARETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| | |
| | 17.) 1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 18.) 1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGTH IN ACCORDANCE WITH TABLE 1511.7. |
| | NOTE:ALTHOUGH A ROOF MOUNTED UNIT IS |
| | NOT SHOWN ON THE PLAN, THIS NOTE IS |
| | MADE TO ASSIST THE DESIGNER IF THIS IS |
| | THE LOCATION OF THE EXISTING OR PROPOSED |
| | UNIT.IF THE UNIT IS OR WILL BE LOCATED |
| | AT ANOTHER LOCATION, DISREGARD THIS |
| | COMMENT. |
| | |
| | 19.)PER FBC 1606.1.7, THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | THERE ARE TWO PARTS TO THIS PLAN; THE |
| | RENOVATION OF THE EXISTING BUILDING AND |
| | THE PROPOSED CARPORT.SOME OF THE ABOVE |
| | INFORMATION IS ON THE PLAN, BUT ALL FIVE |
| | ITEMS IN REGARDS TO THE TWO PARTS OF |
| | THIS JOB ARE NOT ON THE PLAN.PLEASE |
| | REVISE. |
| | |
| | 20.)AWNING WINDOWS ARE INDICATED ON |
| | THE PLAN.IF THEY ARE TO BE CASEMENT, |
| | CHANGE THE PLAN.IF THEY ARE TO BE |
| | AWNING, PROVIDE PRODUCT APPROVALS. |
| | |
| | 21.)THE 2 1/4" RING SHANK NAILS |
| | ON THE WALL SECTION (SHEET D1) DO NOT |
| | MEET THE SHEATHING NAILING REQUIREMENTS. |
| | PLEASE REVISE. |
| | |
| | 22.)PER FBC 2103.1, ENGINEERED MASONRY |
| | SHALL CONFORM TO THE REQUIREMENTS OF |
| | CHAPTERS 1 THROUGH 3 OF ACI 530. LATERAL |
| | TIES REQUIRED IN COLUMNS (ACI 5.9.1.6). |
| | |
| | 23.)PLEASE NOTE:IN REGARDS TO THE |
| | FUTURE POOL, AS PER NEC 680-22(6), |
| | FIXED METAL PARTS THAT ARE WITHIN 5 FT |
| | HORIZONTAL OF THE INSIDE WALL OF THE |
| | POOL ARE REQUIRED TO BE BONDED.YOU |
| | MAY WISH TO MAKE PROVISIONS TO HAVE |
| | THE STEEL FOR THE CARPORT FOUNDATION |
| | BONDED DURING CONSTRUCTION OF THE |
| | CARPORT, BEFORE CONCRETE IS POURED. |
| | THIS IS OPTIONAL AND NOT REQUIRED AT |
| | THIS TIME. |
| | |
| | 24.)PLEASE NOTE: |
| | FBC 1803.1.3 EXCAVATION FOR ANY PURPOSE |
| | SHALL NOT EXTEND WITHIN 1 FT OF THE |
| | ANGLE OF REPOSE OR NATURAL SLOPE OF THE |
| | SOIL UNDER ANY FOOTING OR FOUNDATION, |
| | UNLESS SUCH FOOTING OR FOUNDATION IS |
| | FIRST PROPERLY UNDERPINNED OR PROTECTED |
| | AGAINST SETTLEMENT. |
| | TO ACCOMODATE THE FUTURE POOL, YOU MAY |
| | WISH TO ADDRESS THIS ISSUE AT THIS TIME. |
| | THIS ITEM IS NOT REQUIRED TO BE |
| | ADDRESSED AT THIS TIME. |
| | |
| | 25.)AS PER FBC TABLE 600, NOTE (I), |
| | THE FIRE RESISTANCE REQUIREMENTS FOR |
| | EXTERIOR WALLS WITH 5 FEET OR LESS |
| | HORIZONTAL SEPARATION SHALL BE BASED |
| | UPON BOTH INTERIOR AND EXTERIOR FIRE |
| | PARTITIONS.IN REGARDS TO THE INFILL |
| | WOOD FRAME WALL DETAIL FOR THE WEST |
| | EXTERIOR WALL, EITHER PROVIDE FIRE |
| | RESISTANCE CALCULATIONS (USING FBC |
| | CHAPTER 7) OR CHANGE THAT DETAIL TO |
| | A BLOCK INFILL. |
| | |
| | 26.)BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE ACTUAL PERMIT PLANS |
| | MUST BE STAMPED BY THAT OFFICE, AND A |
| | COPY OF THE PAID RECEIPT ATTACHED TO |
| | THE PERMIT APPLICATION.PLEASE CALL |
| | (561) 233-5025 FOR MORE INFORMATION. |
| | THIS CAN BE DONE AFTER THE PLANS HAVE |
| | BEEN APPROVED BUT BEFORE THE PERMIT CAN |
| | BE ISSUED, OR CAN BE DONE NOW.WHEN |
| | IMPACT FEES ARE PAID, HAVE THEM STAMP |
| | PAGE A1 WHICH HAS THE ZONING & HISTORIC |
| | APPROVALS ON THEM. |
| | |
| | 27.)IN REGARDS TO THE 8X16 BEAM AT THE |
| | DINING ROOM ON SHEET A1, IS THIS |
| | EXISTING OR PROPOSED?IF THIS IS NEW, |
| | PROVIDE A DETAIL AS TO HOW THIS WILL |
| | BE STRAPPED. |
| | |
| | 28.)PLEASE PROVIDE A DETAIL FOR THE |
| | GIRDER AT THE DINING ROOM AND |
| | INFORMATION AS TO HOW THIS WILL TIE |
| | INTO THE EXISTING COLUMNS. |
| | |
| | 29.)PLEASE CLARIFY - IT APPEARS THAT |
| | THERE IS AN EXISTING 8" COLUMN IN THE |
| | KITCHEN THAT IS TO REMAIN.IF THIS IS |
| | TO BE A NEW COLUMN, PROVIDE A DETAIL. IF |
| | THIS IS EXISTING, INDICATE ON PLAN. |
| | |
| | 30.)HOW IS THE STEEL COLUMN TO BE |
| | ATTACHED AT THE TOP?IF THE DETAIL IS |
| | THE SAME AT THE TOP PLATE AS THE BOTTOM, |
| | IT APPEARS THAT THE DETAIL WILL NOT |
| | WORK DUE TO THE DISTANCE OF THE BOLTS |
| | TO THE EDGE OF THE BEAM.EITHER PROVIDE |
| | INFORMATION AS TO HOW THAT DETAIL WILL |
| | WORK AT THE TOP OF THE COLUMN, OR |
| | PROVIDE AN ATTACHMENT DETAIL FOR THE |
| | TOP. |
| | |
| | 31.)PLEASE GIVE INFORMATION IN |
| | REGARDS TO THE LANDINGS SHOWN ON THE |
| | FRONT ELEVATIONS.GIVE HEIGHT FROM |
| | GRADE TO TOP OF LANDING, HEIGHT FROM |
| | TOP OF LANDING TO FINISHED FLOOR, AND |
| | WIDTH AND LENGTH. |
| | |
| | 32.)A SEPARATE PERMIT IS REQUIRED |
| | FOR THE DRIVEWAY APPROACH.AN APPROVED |
| | PLAN IS AVAILABLE FROM THE CITY. |
| | |
| | 33.)ADDITIONAL FEES DUE.THIS MAY |
| | BE PAID WHEN THE PERMIT IS ISSUED. |
| | |
| | 34.)PLEASE GIVE INFORMATION ABOUT |
| | THE GIRDER AT THE DINING ROOM, INCLUDING |
| | ATTACHMENT DETAILS. |
| | |
| | 35.)THE AREA CALCULATIONS ARE NOT |
| | CORRECT.THEY SHOULD INCLUDE ROOFED |
| | AREAS ONLY.THE CARPORT IS NOT ON THE |
| | AREA CALCULATIONS AND AN OVERALL |
| | DIMENSION IS NOT GIVEN FOR THE ROOFED |
| | AREA OF THE CARPORT.PLEASE REVISE. |
| | |
| | 36.)PLEASE PROVIDE A SURVEY, IF |
| | AVAILABLE. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS |
| | NECESSARY.THIS WILL HELP TO EXPEDITE |
| | THE PROCESSING OF YOUR PERMIT. |
| | |