| Plan Review Notes For Permit 03030708 |
| Permit Number |
03030708 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-08-01 00:00:00 | FAILED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE ADDRESS THE FOLLOWING COMMENTS | | | AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT ALL PLANS | | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | | ENGINEER AND 61G1-16.004 FOR ARCH. | | | SHALL HAVE A TITLE BLOCK. | | | | | | 2} REMOVE THE DISCONNECT THAT IS AHEAD | | | OF THE METERS. FPL WILL NOT HOOK UP TO | | | AN UNMETERED SERVICE. | | | | | | 3} REDRAW RISER TO SHOW LOCATION OF | | | RISER AND SERVICE CONDUCTOR SIZE. | | | | | | 4} PLEASE RECALCULATE THE LOADS TO | | | REFLECT THE CORRECT LIGHTING LOAD PER | | | TABLE 220-3(A).* | | | | | | 5} SHOW CONTINUOUS LOADS PER 210-19 | | | (125%) * | | | | | | 6} LIST THE REQUIRED SIGN CIRCUIT PER | | | 600-5.* | | | | | | 7} THE DEMAND FACTORS USED IN THE LOAD | | | CALCULATION ARE FOR DWELLING UNITS AND | | | ARE NOT ALLOWED TO BE USED IN | | | COMMERCIAL APPLICATIONS.PLEASE | | | RECALCULATE USING ALLARTICLES THAT | | | APPLY. | | | | | | PLEASE SEE ATTACHED FLORIDA STATUTE 553. | | | 80(2)(B). * DENOTES COMMENTS ON PAST | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|