| Plan Review Notes For Permit 03030699 |
| Permit Number |
03030699 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-08-19 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE COMPLETE RISER DIAGRAM | | | TO INCLUDE PANEL. | | | | | | 2)NOTE: PLEASE VERIFY SIZE OF PANEL, | | | SERVICE CONDUCTORS ARE SHOWN FOR A 200A | | | SERVICE? | | | | | | 3)NOTE: PLEASE SEE THAT WASHER IS SHOWN | | | AS OPTIONAL? PLEASE SEE 220.16 AND | | | FBC/PLUMB. WASHER IS REQ'D AND MUST BE | | | AVAILABLE. | | | | | | 4)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR, NOTE TO HOUSE STEEL, PLEASE | | | SEE 250.50, THIS SHOULD NOTE TO FOOTER | | | STEEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|