| Plan Review Notes For Permit 03030690 |
| Permit Number |
03030690 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-01-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | A) BATH #2 TUB AND WATER CLOSET ARE NOT | | | VENTED, AND THERE IS NO LAV. | | | B) BATH #1 HAS TWO FIXTURES, (IDENTIFI- | | | ED AS SINKS), AND FLOOR PLAN SHOWS ONE | | | LAV. | | | C) CLEANOUT REQUIRED AT 4' ABOVE THE | | | FLOOR ON WASH MACHINE STACK. 708.10 | | | D) WASH MACHINE REQUIRES A STANDPIPE | | | PER 406.3 | | | E) ALL PIPES SHALL BE SIZED | | | F) THE WASH MACHINE AND KITCHEN SINK | | | ARE NEAR EACH OTHER ON THE FLOOR PLAN, | | | BUT ON OPPOSITE SIDES OF THE HOUSE ON | | | THE SANITARY RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|