| 2004-01-23 00:00:00 | ************** UNSAT ********** |
| | |
| | PLEASE SEE NOTE FROM FIRST TWO REVIEWS. |
| | |
| | 1)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| | (B). PLANS REVIEWED WITH SAME COMMENTS |
| | SUBJECT TO 4X FEE. |
| | |
| | 2)NOTE: PLEASE LIST THE REQUIRED DEDICAT |
| | -ED BATH(S) CIRCUIT(S) PER 210.52D AND |
| | 210.11C3. MUST BE SHOWN AS 20A AND #12 |
| | |
| | 3)NOTE: PLEASE STILL SEE NOTE ON RISER |
| | THAT MENTIONS AND SHOWS OVERHEAD CONDUCT |
| | -ORS FROM METER TO MAIN??? |
| | |
| | 4)NOTE: PLEASE SHOW LOCATION OF PANEL |
| | ON PLANS. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 IN BEDROOMS AND MISSING RECEPT |
| | FRONT OF DWELLING PER 210.52E |
| | |
| | 6)NOTE: PLEASE SEE PLANS, DO NOT SHOW |
| | ELECTRICAL FOR WASHER/ DRYER/ WATER |
| | HEATER??? DISC FOR WH?? |
| | |
| | 7)NOTE: PLAN NOTE MENTIONS DISC REQ'D |
| | IF MORETHAN 8' BETWEEN METER AND PANEL. |
| | PLEASE SEE LOCAL AMENDMENTS. NOTE IS |
| | NOT CORRECT. |
| | LOCAL AMENDMENTS: 230.70A. A MAIN IS |
| | REQ'D ONLY WHEN THERE IS MORE THAN 8' |
| | OF UNPROTECTED(OCP) CONDUCTORS"INSIDE" |
| | THE BLDG. |
| | IF THERE ARE ANY QUESTIONS ON THIS, |
| | PLEASE CALL. |
| | |
| | 8)NOTE: PLEASE SEE LOAD SHOWN FOR A/C |
| | COND UNIT. SHOWS 1200 VA?? |
| | PLEASE ALSO VERIFY MAX OCP FOR 7.5 KW |
| | MIN 125% (424.3) AND MAX 150%. |
| | |
| | 9)NOTE: PLEASE SHOW CONDUCTORS AND |
| | POSSIBLE EQUIPMENT GRND ON LOAD SIDE |
| | OF METER AND MAINDISC IF INSTALLED. |
| | 250.110,250.24, 250.122 |
| | |
| | PLEASE ADDRESS ALL OF THE ABOVE COMMENTS |
| | IF PLANS COME BACK AND ANY OF THE SAME |
| | COMMENTS FROM PREVIOUS REVIEWS ARE NOT |
| | DONE, THEN A 4X FEE WILL BE ACCESED. |
| | PER FS 553.80(2)(B) ATTACHED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |