| Plan Review Notes For Permit 03030690 |
| Permit Number |
03030690 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-11-25 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING REVISIONS TO | | | THE PLAN FOR CODE COMPLIANCE AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE CLARIFY NOTE MENTIONING AND | | | SHOWING OVERHEAD ELECTRIC THE METER AND | | | THE DISCONNECT. | | | | | | 3} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 4} MISSING SMOKE DETECTORS OUTSIDE OF | | | TWO BEDROOMS. | | | | | | 5} LIST BATH RECEPTACLES PER | | | 210.11(C)(3).#12,20 AMP. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|