| Notes |
| Date |
Text |
| 2003-03-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT P-3 BATHROOM BY STAFF NEXT TO | | | STAIR #1, INDICATES TUB TO STAY (1), BUT | | | SHOWS ALL PIPING REMOVED. PLEASE CLAIRFY | | | 2) SHT P.3 ROOMS 1503 & 1504, DOES 2" | | | WASTE REMAIN? NOT DESIGNATED WITH (8). | | | 3) SHTS P-9 & P-11 PLUMBING DRAWING | | | NOTES #'S 3 & 6 FLOOR SINK REQUIRED FOR | | | INDIRECT WASTE. SEC 802.3 (SEE DETAIL ON | | | SHT P-13) | | | - PLUMBING DRAWING NOTES #'S 4 & 5, | | | CONDENSATE SHALL NOT DRAIN INTO SANT. | | | PER CITY CODE 31-62(5). CONDENSATE SHALL | | | BE PIPED SEPARATELY OUT OF THE BLDG. AND | | | TIE INTO STORM SEWER, CATCH BASIN OR DRY | | | WELL. A RELIEF VENT IS REQUIRED AS COND. | | | EXITS BLDG. | | | 4) SHT P-13 ICE MACHINE CONNECTION DE- | | | TAIL, DRAIN FROM CUBER & ICE BIN TO RUN | | | TO THE FLOOR SINK SEPARATELY. | | | 5) SHT P.14 ALL WATER RISER DIAGRAMS, | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | | NOT IN THE CEILING AT THE TOP OF THE | | | DROP AS SHOWN. PDI-WH 201 & MANUFACTURE | | | INSTALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|