| 2003-04-01 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.PLAN SHEET M-7 MECH RM G106, SUPPLY |
| | DUCT TO MECH RM (8" ROUND) APPEARS TO |
| | TERMINATE AT A SIDE WALL.DUCT MUST |
| | CONTINUE WITH NO OPENINGS A MINIMUM OF |
| | 5 FT FROM RATED WALL. 2001 FBC, MECH |
| | 607.1.3. |
| | |
| | 2.PLAN SHEET M-7 24" X 12" OUTSIDE AIR |
| | LOUVER, PENENTRATES A 1 HR WALL - NO |
| | FIRE OR FIRE/SMOKE DAMPER INDICATED. |
| | |
| | 3.PLAN SHEET M-8 EXH DUCT PENETRATING |
| | RM #1B165 & 1B167, RMS HAVE A 1 HR FIRE |
| | RATING - NO DAMPERS INDICATED. |
| | |
| | 4.PLAN SHEET M-8 SUPPLY DUCT PASSING |
| | THROUGH RM #1B187 & 1B185 (RATED WALL) |
| | NO DAMPERS INDICATED. |
| | |
| | 5.PLAN SHEET M-9 DUCT PENETRATING WALL |
| | BETWEEN RM # 1D316 & 1D314 (RATED WALL) |
| | NO DAMPER INDICATED.EXHAUST DUCT |
| | FROM RM # 1D302,(14" X 8"), NO FIRE |
| | DAMPER SHOWN.EXH DUCT AT RM # 1D303 |
| | INTO CORRIDOR 1D300 - NO FIRE DAMPER |
| | INDICATED. |
| | |
| | 6.PLEASE NOTE, PLAN SHEET M-11 SHOWS |
| | (E)RTU3N-2, SUPPLY DUCT TO THIRD FLOOR |
| | & RETURN AIR TO SECOND FLOOR.FLOOR |
| | PLAN INDICATES THIS UNIT SERVES THE |
| | THIRD FLOOR AND DOES NOT GO TO THE |
| | SECOND FLOOR.PLEASE CLARIFY |
| | |
| | 7.PLEASE CLARIFY FLOOR PENETRATIONS. |
| | AS PER 2001 FBC(M) 607.4 BUILDINGS MORE |
| | THAN ONE STORY IN HEIGHT, DUCTS |
| | EXTENDING THROUGH MORE THAN ONE FLOOR |
| | SHALL BE PROTECTED BY A SHAFT ENCLOSURE. |
| | |