Plan Review Notes
Plan Review Notes For Permit 03030678
Permit Number 03030678
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-26 00:00:00************** UNSAT *****************'
  
 1)NOTE: PLEASE SEE RISER DIAGRAM. PLEASE
 CORRELATE RISER AND PANELS SCHEDULES.
 PLEASE SEE OHAC, SHOWN FEEDING X-FORMER
 W/ 100A ON RISER AND 20A ON PANEL?
  
 2)NOTE: PLEASE SUBMIT ALL PANEL SCHEDULE
 -S THAT HAVE PANELS/LOADS BEING ADDED.
 SOME PANEL SCHEDULES ARE MISSING AND
 UNABLE TO COMPLETE REVIEW AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372