| Plan Review Notes For Permit 03030664 |
| Permit Number |
03030664 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-07 00:00:00 | MED GAS VALVES AND ALARM PANEL LOCATION | | | DOES NOT COMPLY WITH NFPA 99C SECTION | | | 4.3.1.2.2 (C) AREA ALARMS. NOTE 2 PANELS | | | SHALL BE LOCATED AT THE NURSES STATION | | | OR OTHER LOCATION THAT WILL PROVIDE FOR | | | SURVEILLANCE. NURSERY STORAGE ROOM DOES | | | NOT MEET THESE REQUIREMENTS. | | | MED-GAS REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|