| Plan Review Notes For Permit 03030664 |
| Permit Number |
03030664 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-26 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | PLAN SHEETS M-3 THROUGH M-6, INDICATE | | | DUCTS INTO SHAFT.SOME OF THE DUCTS | | | INDICATE FIRE/SMOKE DAMPERS & A FEW DO | | | NOT.IT WOULD SEEM THAT ALL DUCTS | | | PENETRATING THIS SHAFT WOULD REQUIRE | | | FIRE/SMOKE DAMPERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|