2003-03-18 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER DIAGRAM.
 SOME PANELS SCH SUBMITTED AND NOTHING
 SHOWN ON RISER? NEED TO SUBMIT PANEL
 SCHEDULE FOR EXISTING PANELS FEEDING NEW
 PLEASE OCP SHOWN IN NOTES, 2P-50A FOR
 63A LOAD??
 LOAD CALCS SHOW "1LC1" AND RISER SHOWS
 "1CL1", ??
  
 2)NOTE: PLEASE NOTE ON PLANS, PANELS
 IN NURSE STORAGE AREA TO BE KEPT CLEAR
 AT ALL TIMES, COMBUSTABLES ETC 110-26
  
 PLEASE SEE FIRE REVIEW COMMENTS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW