| Plan Review Notes For Permit 03030634 |
| Permit Number |
03030634 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-02 00:00:00 | **********PROVISO************ | | | | | | 1.)HURRICANE PROTECTION REQUIRED FOR | | | WINDOW.PLEASE PROVIDE PRODUCT APPROVALS; | | | TWO LEGIBLE COPIES. | | | | | | 2.)PLEASE PROVIDE TWO COPIES OF | | | PRODUCT APPROVALS FOR THE WINDOW AND | | | EXTERIOR DOOR. | | | | | | 3.) STUCCO TO BE 7/8" THICKNESS. | | | | | | 4.)2001 FL BLD CODE, 1005.4: | | | PROVIDE EMERGENCY EGRESS WINDOWS IN | | | SLEEPING ROOMS WITH A MINIMUM NET CLEAR | | | OPENING HEIGTH OF 24" AND NET CLEAR | | | OPENING WIDTH OF 20" AND A NET CLEAR | | | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR | | | OPENINGS ARE PERMITTED TO HAVE A NET | | | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH | | | SHALL NOT BE MORE THAN 44 " ABOVE THE | | | FINISH FLOOR. |
|