Plan Review Notes For Permit 03030456
Permit Number 03030456
Review Stop E
Sequence Number 2
Notes
Date Text
2003-04-09 00:00:00*********** UNSAT *************
  
 PLEASE NOTE, NOW A RISER DIAGRAM IS
 BEING SUBMITTED FOR REVIEW.
  
 1)NOTE: PLEASE SEE PLANS, RISER DIAGRAM
 SHOWS MAIN DISC NEXT TO METER AND PLAN
 LAYOUT ONLY SHOWS METER?
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE NOTE, THESE ARE SEPARATE
 "TOWNHOUSE" UNITS AND LOAD CALCS ARE
 DONE FOR THAT UNIT. PLEASE SEE AND
 CORRELATE LOADS SHOWN ON PANEL SCHEDULE
 AND LOAD CALCS FOR WATER HEATER AND
 RANGE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  