| Plan Review Notes For Permit 03030456 |
| Permit Number |
03030456 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-09 00:00:00 | *********** UNSAT ************* | | | | | | PLEASE NOTE, NOW A RISER DIAGRAM IS | | | BEING SUBMITTED FOR REVIEW. | | | | | | 1)NOTE: PLEASE SEE PLANS, RISER DIAGRAM | | | SHOWS MAIN DISC NEXT TO METER AND PLAN | | | LAYOUT ONLY SHOWS METER? | | | PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE NOTE, THESE ARE SEPARATE | | | "TOWNHOUSE" UNITS AND LOAD CALCS ARE | | | DONE FOR THAT UNIT. PLEASE SEE AND | | | CORRELATE LOADS SHOWN ON PANEL SCHEDULE | | | AND LOAD CALCS FOR WATER HEATER AND | | | RANGE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|