| 2003-05-06 00:00:00 | DENIED:PLANS M-201 & M-202 | | | COMMENTS NOT ADDRESSED FROM 1ST AND 2ND | | | REVIEW. | | | PROVIDE OUTSIDE AIR CALCS AS PER 2001 | | | FBC(M) 402.2 FOR NATURAL VENTILATION OR | | | TABLE 403.3 FOR MECHANICAL.PLEASE | | | PROVIDE CALCULATIONS ON PLAN. | | | | | | PLEASE NOTE PLAN SHEET M-204 AHU | | | MOUNTING DETAIL, DETAIL INDICATES 3" | | | CLEARANCE FOR DUCT CONNECTION.2001 | | | FBC(M) 603.1.3, A MIN OF 4" CLEARANCE | | | IS REQUIRED. | | | | | | PLANS BY ARS DATED 4/29/03 ARE OKAY | | | WITH THE EXCEPTION OF OUTSIDE AIR CALCS. | | | | | | PLEASE REMOVE MECHANICAL PLANS THAT WILL | | | NOT BE USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|