Plan Review Notes
Plan Review Notes For Permit 03030453
Permit Number 03030453
Review Stop M
Sequence Number 3
Notes
Date Text
2003-05-06 00:00:00DENIED:PLANS M-201 & M-202
 COMMENTS NOT ADDRESSED FROM 1ST AND 2ND
 REVIEW.
 PROVIDE OUTSIDE AIR CALCS AS PER 2001
 FBC(M) 402.2 FOR NATURAL VENTILATION OR
 TABLE 403.3 FOR MECHANICAL.PLEASE
 PROVIDE CALCULATIONS ON PLAN.
  
 PLEASE NOTE PLAN SHEET M-204 AHU
 MOUNTING DETAIL, DETAIL INDICATES 3"
 CLEARANCE FOR DUCT CONNECTION.2001
 FBC(M) 603.1.3, A MIN OF 4" CLEARANCE
 IS REQUIRED.
  
 PLANS BY ARS DATED 4/29/03 ARE OKAY
 WITH THE EXCEPTION OF OUTSIDE AIR CALCS.
  
 PLEASE REMOVE MECHANICAL PLANS THAT WILL
 NOT BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.