2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 DESIGN MANUAL
  
 1) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
  
 A) SHT A3.02 OPTIONAL BATHROOMS UNITS
 B & B(REV), W/C SHALL BE 18" OFF WALL
 AND NOT THE SHOWER. TOILETS POSITIONED
 BESIDE A WALL OFFER THE HIGHEST DEGREE
 OF SAFE USE SINCE A GRAB BAR CAN BE
 MOUNTED TO THE SIDE OF THE TOILET. P-6.5
 (THIS IS ALSO THE CASE FOR UNITS IN THE
 FLOOR PLAN)
 B) SHT A3.03 THE CLEAR FLOOR SPACE DIME-
 NTIONS ARE TO BE APPLIED OR SUPERIMPOSED
 OVER A PLAN DURING THE DESIGN PROCESS TO
 DETERMINE OF SPACE REQUIREMENTS AT
 TOILETS ARE BEING MET. P-7.43 - THIS IS
 NOT SHOWN ON "C" OR "C"(REV) UNITS.
 ******** WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.