| Plan Review Notes For Permit 03030362 |
| Permit Number |
03030362 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-12-29 00:00:00 | ************** UNSAT ***************** | | | | | | ***OWNER BUILDER PERMIT MAT NOT BE | | | PULLED DUE TO PRIOR PERMITS ISSUED TO | | | SAME OWNER PER FS 489 | | | THIS WAS COMMENTED ON PREVIOUS REVIEW | | | AND IS STILL COMING BACK WITH OUT A | | | CONTRACTOR. | | | | | | 1)NOTE: PLEASE SEE THAT ONE SET OF PLANS | | | IS NOW BEING KEPT ON FILE FOR RECORD | | | FOR VIOLATIONS UNDER FS 471 AND FAC | | | 61G15-23.002 | | | PLANS ARE STILL MISSING INFORMATION AS | | | REQUIRED UNDER THE ABOVE FS /FAC. | | | PLANS WILL BE KEPT TO BE TURNED INTO | | | THE FBPE'S FOR SAID VIOLATIONS. | | | | | | 2)NOTE: PLANS STILL DO NOT SHOW BATHS | | | AS 20A AS PER 210.11C3. | | | PREVIOUS COMMENT. | | | | | | 3)NOTE: PLEASE SEE THAT LOAD CALCULATION | | | -S HAVE NOT BEEN REVISED DUE TO COMMENT | | | FOR AHU HEAT. PLANS NOW SHOW 10 KW. | | | PLEASE ADJUST. | | | | | | 4)NOTE: PLEASE SEE 424.3B FOR OCP OF | | | AHU/ HEAT. SHOWN AS 30A'S. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW EITHER WHEN SUBMITTED BY A CONTR- | | | -ACTOR OR AFTER TIME IN FS HAS BEEN | | | REACHED. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|