2003-12-29 00:00:00************** UNSAT *****************
  
 ***OWNER BUILDER PERMIT MAT NOT BE
 PULLED DUE TO PRIOR PERMITS ISSUED TO
 SAME OWNER PER FS 489
 THIS WAS COMMENTED ON PREVIOUS REVIEW
 AND IS STILL COMING BACK WITH OUT A
 CONTRACTOR.
  
 1)NOTE: PLEASE SEE THAT ONE SET OF PLANS
 IS NOW BEING KEPT ON FILE FOR RECORD
 FOR VIOLATIONS UNDER FS 471 AND FAC
 61G15-23.002
 PLANS ARE STILL MISSING INFORMATION AS
 REQUIRED UNDER THE ABOVE FS /FAC.
 PLANS WILL BE KEPT TO BE TURNED INTO
 THE FBPE'S FOR SAID VIOLATIONS.
  
 2)NOTE: PLANS STILL DO NOT SHOW BATHS
 AS 20A AS PER 210.11C3.
 PREVIOUS COMMENT.
  
 3)NOTE: PLEASE SEE THAT LOAD CALCULATION
 -S HAVE NOT BEEN REVISED DUE TO COMMENT
 FOR AHU HEAT. PLANS NOW SHOW 10 KW.
 PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE 424.3B FOR OCP OF
 AHU/ HEAT. SHOWN AS 30A'S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW EITHER WHEN SUBMITTED BY A CONTR-
 -ACTOR OR AFTER TIME IN FS HAS BEEN
 REACHED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  