| Plan Review Notes For Permit 03030362 |
| Permit Number |
03030362 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-23 00:00:00 | **PLANS WERE OUTFRONT DENIED BY ZONING** | | | ******* TO ELECTRICAL 4/23/03*********** | | | PLEASE NOTE, OWNER/BLDR PERMIT CAN NOT | | | BE PULLED. FS 489 | | | *************** UNSAT******************* | | | | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPT FOR | | | KITCHEN COUNTERSPACE PER 210-52C-1 | | | PLEASE ALSO SEE MISSING RECEPT FOR | | | KITCHEN PENINSULAR 210-52C2/3, ALSO GFI. | | | 210-8A-6 | | | | | | 2)NOTE: PLEASE SEE MISSING HALLWAY | | | RECEPTS PER 210-52H | | | | | | 3)NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) AS 20A /#12 AWG. 210-52D/ | | | 210-11C-3 | | | | | | 4)NOTE: PLEASE SEE GROUNDING ELECTRODE, | | | NEEDS TO BE SHOWN TO FOOTER STEEL ALSO | | | PER 250-50. | | | | | | 5)NOTE: PLEASE SHOW SIZE OF SEC'S, ARE | | | THEY THE SAME AS CONDUCTORS FROM METER | | | TO MAIN? | | | | | | 6)NOTE: PLEASE CORRELATE SIZE OF HEAT- | | | -STRIP. ELECTRICAL PLAN SHOWS 5KW(SMALL | | | FOR A HOUSE THIS SIZE) A/C PLAN SHOWS | | | 10KW? | | | | | | 7)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210-52 MASTER BR. | | | | | | PLEASE ADJUST LOAD CALCS UPON REVISED | | | A/C HEAT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|