| Plan Review Notes For Permit 03030352 |
| Permit Number |
03030352 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-02 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT ONE SET OF LOAD | | | CALCULATIONS FOR NEW AND EXISTING. | | | | | | 2)NOTE: PLEASE SEE NOTES, #11 MENTIONS | | | NEW 150A SERVICE AND NO RISER DIAGRAM | | | WAS SUBMITTED? PLEASE SUBMIT, SEC`S | | | CONDUITS, AIC RATING FOR NEW MAIN/PANELS | | | ETC. ETC. 215-5/110-9 | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXSITING | | | WATER HEATER AND LOAD? NOT SHOWN ON | | | EXISTING OR NEW LOAD CALCS? | | | | | | 4)NOTE: PLEASE RECONFIURE LOAD CALCS | | | TO MEET NEC 220. | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210-52 ON WALL OUTSIDE BEDROOM. SITTING | | | ROOM? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|